3.
INSTALLATION
THE BURNER MUST BE INSTALLED IN CONFORMITY WITH LEGISLATION AND LOCAL STANDARDS.
!
3.1 WORKING POSITION
The burner is designed to work only in the positions 1, 2 and 3.
!
Installation 1 is preferable, as it is the only one that allows performing maintenance operations as de-
scribed in this manual. Installations 2 and 3 allow working operations but not maintenance with hook-
ing to the boiler.
Any other position could compromise the correct working of the appliance.
Installations 4 and 5 are forbidden for safety reasons.
1
3.2 BOILER FIXING
Fit the flame pipe (1) to combustion head assembly (2).
Adjust slot opening as given in the table on page 8, tighten the screws (3, fig. 2) with a torque no higher
than 10 Nm.
Fit the flange (4), the screw and the two nuts (see fig. 2).
If necessary, widen the insulating gasket holes (5, fig. 3), taking care not to damage them.
Fix the flange (4) to the boiler door (6, fig. 4) interposing the insulating gasket (5), using the screws
(7) and (if necessary) the nuts (8).
Fig. 2
3
E9296
Fig. 3
D5012
3221
2
4
1
2
5
3
WARNING
Boiler door must have a max. thickness of 110 mm, re-
fractory lining included.
5
4
7
7
4
GB
4
5
6
Fig. 4
D7297
8
E9297