Press the START/STOP key to start the
measurement.
START/STOP
During measurements the instrument will beep every 10 seconds to alert the user that a high voltage
is present.
Press the START/STOP key again to stop the measurement. The instrument continues to measure
external voltages but the test result remains displayed on the main display unit.
To ensure your safety, the instrument will automatically discharge the circuit under test, allow for the
voltage displayed to fall back below 25 V before disconnecting the leads.
Press the DISPLAY key to display:
Before the measurement
(2 presses)
During the measurement
(2 presses)
DISPLAY
After the measurement
(5 presses)

3.3. MEASUREMENT OF THE PI

Set the switch to one of the insulation
measurement positions.
1000V
1000V
4T Ω
4T
OFF
the voltage present on the device to be tested,
the test voltage,
the surface leakage current.
the test voltage,
the instantaneous insulation resistance value,
the duration of the measurement,
the current flowing in the resistance being measured.
the voltage present on the device tested,
the insulation resistance value just before the measurement
was stopped,
the duration of the measurement,
the test voltage generated during the measurement,
the current that flowed in the resistance measured,
the surface leakage current,
the capacitance.
Start the measurement by a long press on
the START/STOP key. The long press is
acknowledged by an audible beep.
1
V
> 2s
START/STOP