Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 43
4-3. LOCKING THE OPERATION MODE OF THE AIR CONDITIONER (COOL, DRY, HEAT)
• Description of the function:
With this function, once the operation mode is locked to either COOL/DRY mode
or HEAT mode, the air conditioner operates in that mode only.
* Changing the setting is required to activate this function. Please explain about
this function to your customers and ask them whether they want to use it.
[How to lock the operation mode]
1) Be sure to turn off the main power for the air conditioner before making the
setting.
2) Set the "1" of SW1 on the outdoor display board to ON to enable this function.
3) To lock the operation mode in COOL/DRY mode, set the "2" of SW1 on the
outdoor display board to OFF. To lock the operation in HEAT mode, set the
same switch to ON.
4) Turn on the main power for the air conditioner.
4-4. LOWERING THE OPERATION NOISE OF THE OUTDOOR UNIT
• Description of the function:
With this function, the operating noise of the outdoor unit can be lowered by reducing the operation load, for example, during nighttime in COOL mode.
However, please note that the cooling and heating capacity may lower if this function is activated.
* Changing the setting is required to activate this function. Please explain about this function to your customers and ask them whether they want to use it.
[How to lower the operating noise]
1) Be sure to turn off the main power for the air conditioner before making the
setting.
2) Set the "3" of SW1 on the outdoor display board to ON to enable this function.
3) Turn on the main power for the air conditioner.
4-5. TEST RUN
• Test runs of the indoor units should be performed individually. See the installation manual coming with the indoor unit, and make sure all the units operate
properly.
• If the test run with all the units is performed at once, possible erroneous connections of the refrigerant pipes and the indoor/outdoor unit connecting wires
cannot be detected. Thus, be sure to perform the test run one by one.
Make sure that the following is done.
• Power is supplied to the unit.
• Stop valves are open.
About the restart protective mechanism
Once the compressor stops, the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner.
4-6. EXPLANATION TO THE USER
• Using the OPERATING INSTRUCTIONS, explain to the user how to use the air conditioner (how to use the remote controller, how to remove the air filters,
how to remove or put the remote controller in the remote controller holder, how to clean, precautions for operation, etc.).
• Recommend the user to read the OPERATING INSTRUCTIONS carefully.

5. PUMPING DOWN

When relocating or disposing of the air conditioner, pump down the system following the procedure below so that no refrigerant is released into the atmosphere.
1) Turn off the breaker.
2) Connect the gauge manifold valve to the service port of the stop valve on the gas pipe side of the outdoor unit.
3) Fully close the stop valve on the liquid pipe side of the outdoor unit.
4) Turn on the breaker.
5) Start the emergency COOL operation on all the indoor units.
6) When the pressure gauge shows 0.05 to 0 MPa [Gauge] (approx. 0.5 to 0 kgf/cm
stop the operation. (Refer to the indoor unit installation manual about the method for stopping the operation.)
* If too much refrigerant has been added to the air conditioner system, the pressure may not drop to 0.05 MPa [Gauge] (approx. 0.5 kgf/cm
tion function may operate due to the pressure increase in the high-pressure refrigerant circuit. If this occurs, use a refrigerant collecting device to collect
all of the refrigerant in the system, and then recharge the system with the correct amount of refrigerant after the indoor and outdoor units have been
relocated.
7) Turn off the breaker. Remove the pressure gauge and the refrigerant piping.
When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes.
The compressor may burst and cause injury if any foreign substance, such as air, enters the pipes.
En-10
), fully close the stop valve on the gas pipe side of the outdoor unit and
2
WARNING
COOL/DRY
HEAT
Lower the operating noise
), or the protec-
2

Hide quick links:

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

Mxz-2f42vf2Mxz-2f53vfh2Mxz-2f53vf2

Tabla de contenido