C. After the humidity in the room is dehumidified, when the humidity drops below
2% of the set humidity, the compressor is turned off and the dehumidification is
stopped. The indicator lamp (OK lamp) that reaches the humidity is on.
D. If the dehumidifier stops dehumidifying and the humidity in the room rises above
or equal to 3% or more of the set humidity, if the compressor has passed the
three-minute protection status, the compressor will start dehumidifying.
E. According to the above cycle operation, the indoor humidity can be maintained
at the set humidity.
2.
Comfort (shows "AU") function:
A. Below 5°C at room temperature, the dehumidifier stops;
B. 5 °C ≤ room temperature ≤ 20 °C, automatic selection set 60% humidity;
C. 20°C<room temperature ≤27°C, automatically select setting 55% humidity;
D. Room temperature> 27 °C, automatic selection set 50% humidity.
3.
Drying function: (CLOTH light):
A. When this function is enabled, the dehumidifier will continue to operate
(compressor, fan operation) regardless of the humidity level when the "CO"
(continuous) operation dehumidifies.
B. The wind speed is locked at high speed and cannot be adjusted.
4.
Fan:
A. The compressor does not work.
B. The fan can choose two operating modes: high wind and low wind.
C. Humidity setting button cannot be pressed in fan mode
5.
Full water protection:
A. When the full water lasts for 3 seconds , the controller stops working and all
outputs are turned off. The full water indicator is on (FULL, the buzzer sounds 15
rings. Press any key, the bee The alarm will stop immediately.
B. When the full water fault is removed, the original machine's operating status is
restored (the compressor must be protected by 3 minutes)
6.
Defrost function:
A. When it is in defrosting, the compressor is turned off, the fan is defrosted by high
winds, and the defrost indicator lights up (DEF).
B. When the room temperature is less than or equal to 16°C, the temperature of the
coil is not detected. According to the room temperature action, it is as follows:
Room temperature <5°C, the controller stops.
When 5°C ≤ room temperature ≤ 12°C, the compressor is running for 30 minutes
and the defrost is stopped for 10 minutes.
When 12°C< room temperature ≤ 16°C, the compressor is running for 45 minutes
and the defrost is stopped for 10 minutes
C. When the room temperature is greater than 16°C, the temperature of the coil
is detected, and the operation is performed according to the temperature of
the coil, as follows: When the compressor is running for 30 minutes, the coil
temperature is detected. If the coil temperature is ≤ 1°C, the defrosting is stopped
for 10 minutes.
7.
Compressor delay protection:
A. Every time the boot compressor is allowed to start immediately.
B. After the compressor is shut down, start it again, with at least a 3-minute interval.