12.- ¿Can power consumption points be connected directly to the wind turbine?
No, because the energy they produce is not a controlled and regulated
energy, so an intermediate stabilizer/controller is required. Without such a
stabilizer/controller, our installation will not work correctly.
In the case of remote installations, this stabilizer/controller is the battery.
When the installation is for grid connection, the stabilizer is the grid
connection inverter.
13.- ¿What kind of power is generated by the alternator?
The wind turbine provides an AC three-phase signal which, in remote
installations, has a nominal voltage of approximately 15 Vac, 30 Vac, or
60 Vac depending on the voltage. When grid connected, the nominal
voltage is 150 Vac.
These voltages are later rectified by the regulator passing the power to DC
at 12 Vdc, 24 Vdc, or 48 Vdc to charge batteries, or 120 Vdc to supply the
grid connection inverter.
14.- ¿Should some protection be installed between the wind turbine and the
regulator or between the regulator and the battery?
No, never. The regulator is already carrying out these protective functions.
If you were to install intermediate protection and this disconnected the
electrical connection, the wind turbine would lose its charge and this
could cause irreparable damage to the wind turbine or the regulator.