Class 4 Status Codes - Fronius Symo 10.0-3 208-240 Manual De Instrucciones

Inversores para instalaciones fotovoltaicas acopladas a la red
Ocultar thumbs Ver también para Symo 10.0-3 208-240:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Code
Description
305
No feed-in despite closed relay
There is insufficient PV power for grid
306
power feed operation
DC low
307
DC input voltage is too low for grid
power feed operation
IMPORTANT! Status codes 306 (Power low) and 307 (DC low) appear naturally every morning and evening due
to low solar irradiance. These status codes are not the result of a fault.
308
Intermediate circuit voltage too high
309
DC input voltage MPPT1 too high
311
DC strings polarity reversed
313
DC input voltage MPPT2 too high
314
Timeout current sensor calibration
315
AC current sensor fault
316
InterruptCheck fail
325
Overtemperature in connection area
326
Fan 1 error
327
Fan 2 error
*) If status code persists: Contact a Fronius-trained service technician
**) Fault is corrected automatically. If this status code keeps recurring, contact your system
installer
Class 4 Status
Class 4 status codes may require the intervention of a trained Fronius service technician.
Codes
Code
Description
401
Communication with power module is
not possible
406
AC module temperature sensor faulty
(L1)
407
AC module temperature sensor faulty
(L2)
408
Direct component measured in the sup-
ply grid too high
412
The "fixed voltage" setting has been se-
lected instead of MPP voltage operation
and the voltage is set to a value that is
too low or too high.
415
Safety cut-out triggered by option card or
RECERBO
416
No communication between power mod-
ule and control unit
52
Behavior
Short interruption of grid power
feed operation.
The inverter returns to the
startup phase.
Short interruption of grid power
feed operation.
The inverter returns to the
startup phase.
Short interruption of grid power
feed operation.
The inverter returns to the
startup phase.
Short interruption of grid power
feed operation.
The inverter returns to the
startup phase.
Behavior
The inverter will automati-
cally attempt to connect
again and, if possible, re-
sume feeding energy into
the grid
-
Inverter does not feed ener-
gy into the grid.
The inverter will automati-
cally attempt to connect
again and, if possible, re-
sume feeding energy into
the grid
Remedy
**)
Wait for sufficient solar
radiation;
**)
**)
*)
Remedy
*)
**)
*)
*)