Vaillant sensoHOME VRT 380f Manual De Uso E Instalación página 15

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

MENU → SETTINGS → Installer level → Installation configuration
The installed temperature sensor measures the current room temperature. The control calcu-
lates a new target room temperature that is used to adjust the flow temperature.
– Difference = Set target room temperature - current room temperature
– New target room temperature = Set target room temperature + difference
Prerequisite: In the Zone assignment: function, the control and/or the remote control is as-
signed to the zone in which the control or remote control is installed.
The Room temp. mod.: function is ineffective if No assignmt is activated in the Zone as-
signment: function.
→ Control type:
→ Zone
→ Zone activated:
→ Zone assignment:
→ Zone valve status:
→ Domestic hot water
→ Cylinder:
→ Target flow temperature: °C
→ Circulation pump:
→ Anti-legio. day:
→ Anti-legio. time:
→ Radio link
→ Control reception strength: Read the reception strength between the radio receiver unit
→ OT sensor reception
strength:
→ Screed drying profile
0020298974_00 sensoHOME Operating and installation instructions
Product description 2
2-point
Corresponds to an on/off control system
Analog.
Corresponds to a modulating control system
Deactivate zones that are not required. All existing zones
appear in the display.
Assign the control to the selected zone. The control must
be installed in the selected zone. The control system also
uses the room temperature sensor for the assigned unit.
The Room temp. mod.: function is ineffective if you have
not assigned a zone to the control.
If there is an existing domestic hot water cylinder, the Act-
ive setting must be selected.
Define the days on which you want the anti-legionella func-
tion to run. On these days, the water temperature is in-
creased to above 60 °C. The circulation pump is activated.
The function ends after 120 minutes at the latest.
If the Absence function is activated, the anti-legionella
function is not carried out. As soon as the Absence func-
tion ends, the anti-legionella function is carried out.
Define the time at which you want the anti-legionella func-
tion to run.
and outdoor temperature sensor.
– 4: The radio link is within the acceptable range. If the
reception strength is < 4, the radio link is not stable.
– 10: The radio link is highly stable.
Read the reception strength between the radio receiver unit
and outdoor temperature sensor.
– 4: The radio link is within the acceptable range. If the
reception strength is < 4, the radio link is not stable.
– 10: The radio link is highly stable.
Setting target flow temperature per day in accordance with
the construction regulations
13

Hide quick links:

Tabla de contenido
loading

Tabla de contenido