Wiring AC Power and Control Terminals
The following Attention statements apply to the wiring diagram on the facing page:
ATTENTION: This equipment is at line voltage when AC power is
connected. Disconnect and lockout all ungrounded conductors of the
!
AC power line before working on the unit. Failure to observe this
precaution could result in severe bodily injury or loss of life.
ATTENTION: Many local and national electrical codes require that an
input disconnect be provided in the incoming power lines. Failure to
observe this precaution could result in severe bodily injury or loss of
life.
ATTENTION: Many local and national electrical codes require that
upstream branch protection be provided to protect input power wiring.
Failure to observe this precaution could result in severe bodily injury
or loss of life.
ATTENTION: If the distribution system capacity exceeds the drive's
maximum symmetrical fault short-circuit current of 100,000 amps,
additional impedance must be added to the AC line supplying the drive
to limit available current in the event of a fault. Failure to observe this
precaution could result in damage to, or destruction of, the equipment.
ATTENTION: The user must provide an external, hardwired
emergency stop circuit outside of the SP200 drive circuitry. This circuit
must disable the system in case of improper operation. Uncontrolled
machine operation may result if this procedure is not followed.Failure
to observe this precaution could result in severe bodily injury or loss
of life.
ATTENTION: If 2-wire control is selected, the drive will immediately
run when powered up in the presence of a forward or reverse run
command. Failure to observe this precaution could result in severe
bodily injury or loss of life.
ATTENTION: The 4-pin circular connector (located directly above the
control terminals) may increase to a hazardous voltage level if the
control shield terminal (terminal 1) is left ungrounded. Failure to
observe this precaution could result in severe bodily injury or loss of
life.
4
SP200 AC Drive Quick Start Guide