Information For Contacting Technical Support; Preventive Maintenance - Weq CFW700 Serie Manual Del Usuario

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Troubleshooting and Maintenance
Problem
Off display
Keypad
connections
Power supply
voltage
Mains supply fuses
open
Motor does not
Settings
operate in the field
weakning region
(Vector Control)
Low motor speed
Encoder signals
and P0009 = P0169
are inverted or
or P0170 (motor
power connection
operating with
is inverted
torque limitation), for
Encoder cable is
P0202 = 5 - vector
broken
with encoder

6.3 INFORMATION FOR CONTACTING TECHNICAL SUPPORT

For technical support and servicing, it is important to have the following information in hand:
Inverter model.
Serial number and manufacturing date available on the identification label of the product (refer
to
section 2.5 IDENTIFICATION LABELS on page 8
Installed software version (check parameter P0023).
Application data and inverter settings.

6.4 PREVENTIVE MAINTENANCE

DANGER!
Always disconnect the general power supply before touching any electric
component associated to the inverter.
High voltages can be present even after the disconnection of the power supply.
Wait for at least 10 minutes for the complete discharge of the power capacitors.
Always connect the frame of the equipment to the protective earth (PE) at the
proper point.
52 | CFW700
Point to be
Verified
1. Check the inverter keypad connection.
1. Rated values shall be within the limits specified below:
200...240 V power supply: (Frame sizes A to D) Minimum:
170 V; Maximum: 264 V.
220 / 230 V power supply: (Frame size E) Minimum: 187
V; Maximum: 253 V.
380...480 V power supply: Minimum: 323 V; Maximum:
528 V.
500...600 V power supply: Minimum: 425 V; Maximum:
660 V.
1. Replace fuses.
1. Decrease P0180.
1. Check the signals A – A, B – B, refer to
19. If signals are properly installed, exchange two of the
output phases. For instance U and V.
1. Replace the cable.
Corrective Action
and the
Figure A.2 on page
Figure 3.6 on page
198).
Tabla de contenido
loading

Tabla de contenido