Weq CFW700 Serie Manual Del Usuario página 49

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Keypad (HMI) and Basic Programming
It is necessary to set the parameter P0223 to 9 = SoftPLC (CW) or 10 = SoftPLC (CCW) together
with P0224 to 4 = SoftPLC, or else, it is necessary to set P0226 to 9 = SoftPLC (CW) or 10 =
SoftPLC (CCW) together with P0227 to 4 = SoftPLC for the operation of the Forward/Reverse Run
application. The following alarm message will be displayed in case the Local FWD/REV selection
is not set (P0223): "A760: Set Local FWD/REV to SoftPLC" and the operation of the application
will not be enabled if the Local Run/Stop selection (P0224) has been set to SoftPLC. The same
applies to the Remote FWD/REV (P0226), i.e., the following alarm message will be displayed:
"A762: Set Remote FWD/REV to SoftPLC" and the operation of the application will not be enabled
if the Remote Run/Stop selection (P0227) has been set to SoftPLC.
Definitions:
The Function 1 of the Application at parameters P0263 to P0270 represents the Forward
command.
The Function 2 of the Application at parameters P0263 to P0270 represents the Reverse
command.
The Forward command is done by one of the digital inputs (DI1 to DI8). It is necessary to set
one of the DI's parameters (P0263 to P0270) to 20 = Function 1 of the Application. If more than
one digital input is set for this function, the logic operation will consider only the command of
the high priority level digital input, where: DI1>DI2>DI3>DI4>DI5>DI6>DI7>DI8. If any digital
inputs is set, the following alarm message will be displayed: "A750: Set a DI for Function 1 of
the Application (Forward)" and the operation of the application will not be enabled. It is defined
that the forward command rotation will always be "clockwise".
The Reverse command is also done by one of digital inputs (DI1 to DI8). However, it is necessary
to set one the DI's parameters (P0263 to P0270) to 21 = Function 2 of the Application. If more
than one digital input is set for this function, the logic operation will consider only the command
of the high priority level digital input, where: DI1>DI2>DI3>DI4>DI5>DI6>DI7>DI8. If any digital
inputs is set, the following alarm message will be displayed: "A752: Set a DI for Function 2 of
the Application (Reverse)" and the operation of the application will not be enabled. It is defined
that the forward command rotation will always be "counterclockwise".
Both Forward and Reverse inputs are active when 24 V is applied and inactive when 0 V is applied.
With the inverter enabled in local or remote mode, with no fault, without undervoltage, no A750,
A752, A760 and A762 alarms, the "General Enable" command is performed in the inverter. In
case some digital input is set to "General Enable" function, the inverter will effectively be enabled
when the two command sources are active.
With the forward digital input active and the reverse digital input inactive, the forward and
start commands are performed. If the reverse digital input is active, nothing is changed in the
operation of the inverter. When both commands are inactive, the start command is removed
and the motor will be decelerated to 0 rpm. However, when the reverse digital input is active
and the forward digital input is inactive, the reverse and start command are performed. If the
forward digital input is active, nothing is changed in the operation of the inverter. When both
commands are inactive, the start command is removed and the inverter decelerates to 0
rpm. In case both forward and reverse digital inputs are active at the same time, the forward
command will be generated.
The parameter related to this application is:
44 | CFW700
Tabla de contenido
loading

Tabla de contenido