S&P CADB-N TERMO-REG 05 Instrucciones De Uso página 52

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

3000 H
9000 H
6000 H
Factory settings:
10.2.1.5. CO
Sensor
2
The fan speed can be managed automatically with connection of external sensor of CO
. The
2
system will increase the speed or reduce the speed in function of the level of CO
measured.
2
For active this function it is necessary to enable the air quality sensor in the menu of confi gura-
tion and select the automatic control of ventilation in the handset.
Factory settings:
10.2.1.6. Change the CO
setpoint
2
In case of working with the fan speed in automatic mode with a CO
sensor. It is possible modify
2
the setpoint, between 800, 1000 and 1200 ppm. By default, is set to 1000 ppm. If you need to
modify the setpoint, follow the following steps:
1. Make sure the parameter CO
Sensor of installer Menu is ON (default OFF).
2
2. Using the ON/OFF button and proceed as follows:
3. With the equipment off, press the FAN button for 5 seconds. When you hear a single "beep"
immediately stop pressing the FAN button. The setting is found in the CO
setpoint parameter.
2
In the LEDS that indicate the fan speed will now be
, blinking, to indicate the current value of
selected setpoint. To modify it, press the FAN. It is possible to select 3 setpoints:
52
Tabla de contenido
loading

Tabla de contenido