Explosion Hazard
Use a new AGA or CSA approved gas supply
line.
Install a shut-off valve.
Securely tighten all gas connections.
If connected to LP, have a qualified person
make sure gas pressure does not exceed 14"
water column. Examples of a qualified person
include licensed heating personnel, authorized
gas company personnel, and authorized
service personnel.
Failure to do so can result in death,
explosion, or fire.
Observe all goveming codesand ordinances.
This installation must conform with all local codes and
ordinances. In the absence of local codes, installation
must conform with American National Standard,
National Fuel Gas Code ANSi Z223.1 -- latest edition*.
Input ratings shown on the model/serial rating plate are
for elevations up to 2,000 feet. For assistance when
installing the range at higher elevations, contact your
local Sears Service Center.
Type of gas: This range is design-certified by the
American Gas Association (A.G.A.) for use with Natural
gas or, after proper conversion, for use with
L. P. gas. This range is factory set for use with Natural
gas. Gas conversion instructions are provided on Pages
22-29. The model/serial rating plate located on the
frame behind the storage drawer has information on
the types of gasthat can be used. If the types of gas
listed do not include the type of gas available, check
with the local gas supplier.
Peligro de explosibn
Use una linea de suministro de gas nueva aprobada
por AGA o CSA.
Instale una v_lvula de cierre.
Apriete con firmeza todas las conexiones de gas.
Si est_ conectada a gas de P.L., haga que una
persona calificada asegure que la presi6n de gas
no exceda de una columna de agua de 14".
Ejemplos de personas calificadas son miembros
del personal de calefacci6n con licencia, personal
autorizado de la compafiia de gas y personal de
servicio autorizado.
No seguir estas instrucciones puede ocasionar la
muerte, una explosibn e un incendio.
Observe todos los c6digos y reglamentos vigentes.
Esta instalacion debe cumplir con todos los c6digos y
reglamentos locales. A falta de c6digos locales, la
instalacJ6n debe cumplir con American National
Standard, National Fuel Gas Code ANSI Z223.1--_ltima
edici6n*.
Las clasificaciones de entrada que se indican en la
placa de modelo/serie
son para elevaciones de hasta
2,000 pies sobre el nivel del mar. Para asistencia
cuando
instale la cocina en lugares con mayor altitud,
contacte
a su Centro de ServicJo Sears.
Tipo de gas: el diseSo de esta cocina ha sido
certificado
pot la American
Gas Association
(A.G.A.)
para uso con gas Natural o, despues de la debida
conversi6n,
para uso con gas de P.L. Esta cocina ha
sido ajustada en la fabrica para uso con gas Natural.
Las instrucciones
de conversi6n
de gas aparecen
en
las paginas 22-29. La placa de modelo/serie
ubicada en
el marco detras del caj6n de almacenamiento,
contiene
informaci6n
sobre el tipo de gas que se
puede usar. Si los tipos de gas indicados
no incluyen
el tipo de gas disponJble,
contacte
a la compaSia
de
gas de su ]ocalidad.
10
manual shutoff valve"open" position,
valvula de cierre manual en la
posicibn "abierta"
to range \
\
hacia la
cocina
gas supply line
linea de suministro
de gas
Conversionmustbe doneby a qualifiedservice technician.
Gas supply line: Provide a gas supply line of 3/4" rigid
pipe to the range location. With L.P. gas, piping or
tubing size can be 1/2" minimum. A smaller size pipe on
longer runs may result in insufficient gas supply.
Usually, LP. gas suppliers determine the size and
materials used in the system.
Pipe-joint compounds made for use with L.P. gas must
be used on pipe threads only.
Flexible metal appliance connector:If local codes
permit, a new A.G.A. design-certified, 1/2" or 3/4" i.D.,
flexible metal appliance connector is recommended for
connecting range to the gas supply line. A 1/2" male
pipe thread nipple is needed for connection to the
female pipe threads of the inlet to the appliance
pressure regulator. Do Not kink or damage the flexible
metal tubing when moving the range.
Rigid pipe connection: Requires a combination of pipe
fittings to obtain an in-line connection to the range. All
strains must be removed from the supply and fuel
lines so range will be level and in line.
Shutoff valve: The supply line must be equipped with
a manual shutoff valve. This valve should be located in
the same room asthe range and should be in a
location that allows ease of opening and closing. The
valve is for turning on or shutting off gas to the range.
Do Not block accessto shutoff valve.
Pressureregulator: The gas pressure regulator supplied
with this range must be used. The inlet pressure to the
regulator should be as follows for proper operation:
NATURAL GAS:
Minimum pressure: 5 inches WCP
Maximum pressure: 14 inches WCP
LP. GAS:
Minimum pressure:11 inches WCP
Maximum pressure:14 inches WCP
Contact local gas supplier if you are not sure about the
inlet pressure.
La conversion debe ser hecha por un tdcnico de servicio
calificado.
Unea de suministro de gas: instale una linea de
suministro
de gas de tubo rigido de 3/4" has,ta la cocina.
Para el gas de P.L., el tubo debe medir un mlnimo de 1/2".
Un tubo mas pequeSo para recorridos
mas largos, podrla
ocasionar un suministro
de gas insuficiente.
Usualmente,
las compaSia
proveedoras
de gas de P.L determinan
las
dimensiones
y los materiales usados en el sistema.
Los compuestos para juntas de tubo disefiados para uso
con gas de P.L. deben usarse L_nicamente en las roscas
del tubo.
Conector de electrodomdsticos de metal flexible: si los
c6digos locales Io permiten, se recomienda usar un
conector de electrodom6sticos de metal flexible con
diametro intemo de 1/2" 6 3/4", con diseSo certificado por
la A.G.A., para conectar ]a cocJna a la linea de suministro
de gas. Se necesita una boquilla acopladora macho de
1/2" para la conexi6n a la rosca de tuberia hembra del
regulador de presi6n. AI mover la cocina, no enrosque ni
dafie el tubo de metal flexible.
Conexi6n con tubo rigido: requiere de una combinaci6n
de accesorios para tubos para Iograr una conexi6n en la
linea a la cocina. Deben eliminarse
las deformaciones
de
las lineas de suministro
y combustible
para que la cocina
este nivelada y en linea.
Valvula de cierre: la linea de sumJnistro
debe estar
equipada
con una valvula de cJerre manual. Esta
valvula debe estar Iocalizada en la misma
habitaci6n
en que esta la cocina, en un lugar que facilite su
apertura
y cierre. El prop6sito de la valvula es generar
o interrumpir
el suministro
de gas a la cocina. No
bloquee el acceso a la valvula de suministro.
Regulador de presi6n: se debe usar el regulador
de
presi6n provisto con esta cocina. Para e] debido
funcJonamiento de la cocina, la presi6n de entrada al
regulador
debe ser como sigue:
GAS NATURAL:
Presi6n minima:
5 pulgadas WCP
Presi6n maxima:
14 pulgadas WCP
GAS de P.L:
Presi6n minima:
11 pulgadas WCP
Presi6n maxima:
14 pulgadas WCP
Si no esta seguro sobre la presi6n de entrada,
consulte
con la compaSia
de gas de su Iocalidad.
11