EN
DIRECT EXPANSION COIL
4 6
3 6
Ø 1
Ø 2
4 0
4 0
CONDENSATE DRAIN.
30
FCX
A
[mm]
B
[mm]
Ø 1
[mm]
Ø 2
[mm]
In all FCX models equipped with a direct
expansion coil (FCX_UE, FCX_PE) the refriger-
ant connections are located on the right; the
control panel or the electrical box must be on
the left side.
In the case of horizontal installation, fit the
condensate drain fitting supplied. Seal the
connection between the tray and the fitting
with silicone.
The condensate drain network must be prop-
erly sized and the pipelines must be posi-
tioned in order to maintain a suitable slope
along the path (min.1%).
In the case of discharge to the sewer, it is
advisable to make a siphon which prevents
22÷50
62÷102
400
522
408
530
9.52
9.52
12
16
ATTENTION: The direct expansion coil is not
reversible.
odours from returning into the environ-
ment.
Run an operating and condensate drain sys-
tem seal test by pouring water in the tray.
FCX P-PE-PO-PV
IFCXPLJ 1412 - 6456063_01