AKO -15651-3 Guía Rápida página 18

Idiomas disponibles

Idiomas disponibles

Component location
Battery connector
Control
terminal
Control
cable
connector
Single phase
terminal
Three phase
terminal
ATTENTION: Make sure to turn of the equipment's power supply before handling it, as different areas
may be energised.
Technical specifications
Rated voltage Un...........................................................................................................400 V~ ±10 % 50 Hz ±5 %
Rated voltage Ue...........................................................................................................230 V~ ±10 % 50 Hz ±5 %
ALARM relay ........................................................................................................................... 8A at 250V, cosj=1
Probe temperature range...........................................................................................................–40.0 ºC to 99.9 ºC
Resolution, setting and differential ................................................................................................................0.1 ºC
Thermometric precision.................................................................................................................................± 1 ºC
Precision of the NTC probe at 25 ºC .............................................................................................................± 0.4 ºC
Input for NTC probe .............................................................................................................................AKO-15561
Maximum input power in the operation ..........................................................................................................30 VA
Working ambient temperature............................................................................................................-5 ºC to 40 ºC
Storage ambient temperature ..........................................................................................................–30 ºC to 70 ºC
Overvoltage category .....................................................................................................................II s/ EN 61439-1
Degree of pollution ........................................................................................................................II s/ EN 61439-1
Degree of protection .......................................................................................................................................IP65
Dimensions .............................................................................................................400(An) x 300(Al) x 135(P) mm
Double isolation between power supply, secondary circuit and relay output.
Logger battery life if the power supply fails..................................................................................................48 hours
Battery ...................................................................................................................................Li-Polymer for logger
Type of assembly................................................................................................................................Fixed internal
Internal buzzer
Encapsulated assembly
18
F1: Circuit breaker
FM: Operating circuit breaker
Q1: Compressor and fan
1 motor guard
Q2: Fan 2 motor
guard
K2M: Defrost
contactor
F2: Auxiliary
output fuse
K1M: Compressor
contactor
K3M: Fan 2 contactor
loading

Este manual también es adecuado para:

Proplus 3phAko-15652-3Ako-15653-3