Cautions
Using the unit not observing the manufacturer's instructions may alter the appliance's safety requirements. Only probes
supplied by AKO should be used for the it to operate correctly.
From –40 ºC to +20 ºC, if the NTC probe is extended to 1000 m with at least 0.5 mm cable, the maximum deviation
will be 0.25 ºC (cable for probe extension ref. AKO-15586).
Versions and references
AKO-15651-3
AKO-15652-3
AKO-15653-3
Recommendations
Disconnect the voltage before carrying out any operations inside the electrical panel. All wiring should be according to
current standards and should be carried out by authorised staff. Only carry out the wiring foreseen in the wiring
diagrams. Using the electrical panel not observing the manufacturer's instructions may alter the appliance's safety
requirements. A tool is needed to remove any fixed part.
Panel installation:
It is advisable to leave a clean safety space without obstacles around the panel.
Do not knock or make sudden movements on the panel.
Carry out the wiring according to the installation manual.
The probes and their cables should NEVER be installed in a conduit together with power, control or feeder cables.
The earth terminals that the panels contain are installed to guarantee the continuity of earthing, however, earthing is
not carried out by the terminal and should be carried out outside the panel.
The neutral ratings are of the TT type. The IT rating should not be used.
Circuit breakers (protective switches) are of the phase/s + neutral, curve C type, guaranteeing switching and protection
against overcurrents.
Close the panel when your are not working on it.
Residual current protection outside the electrical panel according to low voltage electrotechnical regulations.
The panels meet European standard EN 61439-1.
Terminals for copper external conductors.
Checks before starting the panel up:
Power supply voltages and frequencies will be the ones that figure in the "Technical specifications" section.
Check that there are no loose parts or foreign bodies on connections or switchgear.
Check that there is no dust or damp inside the panel.
Check the correct fastening of the switchgear and components.
Check the correct tightening of the screws and power connections.
Check the correct connection of the power conductors.
Check the correct insulation of the outer lines and that they do not mechanically force the inner connections of the panel.
Check that the maximum current of the Q1 current breaker.
Before starting the installation up, we recommend preheating the compressor's housing.
Condensing
Condenser
unit
fans
4 - 6.3 A
0.63 - 1 A
6.3 - 10 A
1 - 1.6 A
10 - 12 A
1 - 1.6 A
Evaporator
Defrost
fan
resistances
7.000 W
3 A
10.200 W
14
2
Light Power supply
2 A
400 V / III
(460 W)
50/60 Hz