Starting Rcd Test With Rcd Tripping, Funtion Trcd/Vc - BEHA Unitest TELARIS Fi/RCD Manual De Instrucciones

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Starting of RCD Test
I∆N:
Display at RCD has tripped
A possible reason could be:
incorrect selection of test current.
a residual current is present within the net to be
tested, causing the RCD to trip early because it
sums up with the test currents.
RCD faulty.
The calculated contact voltage is displayed up
to an votage of 70 V
The measurement is interrupted if the contact vol-
tage exceeds the set contact voltage limit. "Attenti-
on" (1) and "UB>UL" (3) appears on the display.
I∆N:
I∆N:
40
5.2.3
Starting RCD Test with RCD Tripping,
Funtion tRCD/UB
The contact voltage VC is measured during a test,
by applying a current amounting to 40 % of the no-
minal residual current. The contact voltage display-
ed is extrapolated to nominal residual current I∆N
or to double the nominal residual current I∆N for
selective RCDs.
Upon the examnation of RCDs a break of 30
sec is had betweeen pre-test and preliminary
test.
I∆N:
2 x
Connect test lead / mains connection cable
to test instrument.
Connect test lead / mains connection cable
to the UUT, as described in figure 1 or 2.
Select desired measurement function
tRCD/UB using function selection switch
(31).
Set nominal residual current selection (20)
to desired nominal current (depending on
RCD).
Set phase position using key 0° / 180° (24).
Set current type (23) and multiplication fac-
tor using key (30).