SETTINGS FROM AIRTOOLS ON AIRZONE CLOUD
Auxiliary Heat
It is used to activate or deactivate this function and to set configurations:
EN
Delta On (T
Range: -4ºC (-7.2°F) / -1.5ºC (-2.7°F) in steps of 0.5ºC (0.9ºF). Default: -2.5ºC (-4.5ºF).
Delta Off (T
Range: -0.5ºC (-0.9°F) / -1.5ºC (0.9°F) in steps of 0.5ºC (0.9ºF). Default: -0.5ºC (-0.9ºF).
- 4 ºC
T
amb
Auxiliary Heat ON
T
: Zone ambient temperature
zone
Delay time. It configures the delay time for the activation of Auxiliary Heat using
selectable values. Deactivated: 90-second delay.
Type of ventilation. It is used to choose between ducted heating or external auxiliary
heat. Ducted heating relies on the indoor unit ventilation to activate auxiliary heat, and
in External auxiliary heating the ventilation source is independent of the indoor unit.
Heat source lock
This activates or deactivates heat source lock depending on the lock outside temperatures
defined.
Auxiliary Heat Lockout Temperature (T
temperature for locking Auxiliary Heat function activation. If the outside temperature is
above the lock temperature set, the Auxiliary Heat function will not be activated even if
the activation conditions are met (T
T
out
- 14 ºC
Auxiliary Heat Unlocked
T
: Outside temperature
out
14
). Offset applied to the setpoint temperature to activate auxiliary heat.
on
). Offset applied to the setpoint temperature to switch off auxiliary heat.
off
- 1,5 ºC
ΔT
on
T
on
Range: -14ºC (7°F) / 18ºC (64°F) in steps of 2ºC (3.6 ºF). Default: 0ºC (32ºF).
- 0,5 ºC
ΔT
off
T
off
Set-Point
OFF
ON
). It is used to set an outside
Lock Aux.Heat
).
on
T
Lock Aux. Heat
0 ºC
Auxiliary Heat Locked
0,5 ºC
Auxiliary Heat OFF
18 ºC