ProCore Edge North America
Display
Message
Module OVP
Tripped
MODULE TYPE
ERR
(Module
Installation
Type)
No Battery
Configuration
No Modules
OCP Fault
(There is a
Module
Overcurrent)
OVP Fault
(There is a
Module
Overvoltage)
Power Stage
Initialization
Error
31241-03-0202
Message
Description
type
There was an error in the
Fault
over-voltage protection
module.
The power module type
does not match the factory
configuration (cabinet
Fault
voltage) settings, or
incompatible modules were
installed together.
The parameters have not
Fault
been configured for the
voltage mode charge.
No power modules are
Fault
installed.
Fault
The module failed.
The battery became
Fault
disconnected without
opening the pilot.
There was a CAN bus
Fault
problem during power
stage initialization.
64 of 68
Action(s)
Check that the battery
voltage is within range for
the charger.
Install the correct
power module.
Call Webasto service.
Configure the voltage
mode settings on the
charger, using the ProCore
mobile app.
Call Webasto service.
Replace the power module.
Wait for the fault to clear.
Call Webasto service.