Regulation type:
- HYs: regulation of hysteresis
- bP:
regulation of proportional type
Factory setting value: bP
Other values: HYs
Hysteresis value:
This menu is displayed only if parameter "typ" is equal to
"HYs". Use
and
keys to set hysteresis value. The setting
is validated with key
.
Default value: 0.3 °C
Value range: 0.2 °C to 3 °C
Choice of concrete type:
Two choices are possible:
- uf1: for thin liquid concrete < 6 cm
- uf2: for traditional concrete with a thickness higher than 6 cm
if parameter #26 is set to "HYs" this menu is not available.
Factory setting value: uf1
Other values: uf2
Choice of coating:
Two choices are possible:
- bP1: for tiling
- bP2: for wooden floors (floating or not)
if parameter #26 is set to "HYs" this menu is not available.
Factory setting value: bP1
Other values: bP2
Function of pilot wire:
This option is used to enable the pilot wire functionality if it's
used on your installation.
Factory setting value: no
Other values: yes
Minimum value of setting range of the set point
temperature:
Factory setting value: 5.0 °C
Other values: 5.0 °C to 15.0 °C
Maximum value of setting range of the set point
temperature:
Factory setting value: 37.0 °C Other values: 20.0 °C to 37.0 °C
Humidity set point (Optional)
Factory setting value: 75 % Other values: 0 % ("no") to 100 %