Installation
For installation of the indoor unit, refer to the indoor unit
installation manual.
Never operate the unit without the thermistor (R3T, R4T) or
pressure sensors (S1NPH, S1PH), burning of the compressor
may result.
Be sure to confirm the model name and the serial no. of the
outer (front) plates when attaching/detaching the plates to avoid
mistakes.
When closing the service panels, take care that the tightening
torque does not exceed 3.03 lbs•ft (4.1 N•m).
NOTE
An ERLQ0*BA outdoor unit can only be connected to
an EKHBH/X016BA indoor unit (bottom plate heater at
outdoor unit has to be controlled by indoor unit).
Accessories
Check if the following accessories are included with the unit
Installation manual
Cable tie
See the figure below for the location of the accessories.
1
1
Handling
As shown in the figure below, slowly move the unit by grabbing the
left and right grips. Position your hands on the corner instead of
grabbing the air inlet to avoid deforming the casing.
To avoid injury, do not touch the air inlet or aluminium fins
of the unit.
ERLQ036~054BAVJU
Outdoor unit for air to water heat pump
4PW55905-1
1
2
Accessories
S
ELECTING INSTALLATION SITE
CAUTION
Make sure to provide for adequate measures in order
to prevent that the outdoor unit be used as a shelter
by small animals.
Small animals making contact with electrical parts can
cause malfunctions, smoke or fire. Please instruct the
customer to keep the area around the unit clean.
1
Select an installation site where the following conditions are
satisfied and that meets with your customer's approval.
-
Places which are well-ventilated.
-
Places where the unit does not bother next-door neighbours.
-
Safe places which can withstand the unit's weight and
vibration and where the unit can be installed level.
-
Places where there is no possibility of flammable gas or
product leak.
-
The equipment is not intended for use in a potentially
explosive atmosphere.
-
Places where servicing space can be well ensured.
-
Places where the indoor and outdoor units' piping and wiring
lengths come within the allowable ranges.
-
Places where water leaking from the unit cannot cause
damage to the location (e.g. in case of a blocked drain pipe).
-
Places where the rain can be avoided as much as possible.
-
Do not install the unit in places often used as work place.
In case of construction works (e.g. grinding works) where a
lot of dust is created, the unit must be covered.
-
Do not place any objects or equipment on top of the unit (top
plate).
-
Do not climb, sit or stand on top of the unit,
-
Be sure that sufficient precautions are taken, in accordance
with relevant local laws and regulations, in case of refrigerant
leakage.
2
When installing the unit in a place exposed to strong wind, pay
special attention to the following.
Strong winds of 16.40 ft/sec (5 m/sec) or more blowing against
the outdoor unit's air outlet causes short circuit (suction of
discharge air), and this may have the following consequences:
-
Deterioration of the operational capacity.
-
Frequent frost acceleration in heating operation.
-
Disruption of operation due to rise of high pressure.
-
When a strong wind blows continuously on the face of the
unit, the fan can start rotating very fast until it breaks.
Refer to the figures for installation of this unit in a place where
the wind direction can be foreseen.
Turn the air outlet side toward the building's wall, fence or
screen.
Make sure there is enough room to do the installation
Installation manual
3