Faults
Collective fault signal
contact open
Dual-pump function
faulty
If the malfunction cannot be rectified, consult a specialist technician or the nearest Wilo customer ser-
vice or representative location.
11
Spare parts
Obtain genuine spare parts only from a qualified specialist or customer service. To avoid queries and order
errors, please supply all data on the rating plate with every order.
12
Disposal
12.1
Information on the collection of used electrical and electronic products
Proper disposal and appropriate recycling of this product prevents damage to the environment and danger to
your personal health.
NOTICE
Disposal in domestic waste is prohibited!
In the European Union this symbol may be included on the product, the packaging or the ac-
companying documentation. It means that the electrical and electronic products in question
must not be disposed of along with domestic waste.
Please note the following points to ensure proper handling, recycling and disposal of the used products in
question:
Hand over these products at designated, certified collection points only.
Observe the locally applicable regulations!
Please consult your local municipality, the nearest waste disposal site, or the dealer who sold the product to
you for information on proper disposal. See www.wilo‑recycling.com for more information about recycling.
Subject to change without prior notice!
32
Installation and operating instructions • Wilo-Connect Modul Yonos MAXO • Ed.03/2024-02
Cause
A fault has occurred: Pump not running/pump faulty.
Double pumps only:
SSM master pump: One or both participants of
the double pump is/are faulty.
SSM standby pump: Standby pump is defect-
ive.
DIP switch in the master or standby pump in
wrong position.
Dual-pump management connecting cable not
connected.
Connecting cable connected with wrong polarity.
Remedy
Note the error code at
the pump.
Read the installation
and operating instruc-
tions for the pump.
Move DIP switch to a
different position.
Check the dual-pump
management con-
necting cable.
loading