Mando por cable
The wired controller line is a low-voltage circuit, which cannot come
into direct contact with any high-voltage line or share the same
wiring tube with any high-voltage line. The minimum spacing of
wiring tubes should be 300 to 500 mm.
Do not install the wired controller in a corrosive, flammable or
explosive environment or at any place with oil mist (such as a
kitchen).
Do not install the wired controller in damp places. Keep it out of
direct sunlight.
Do not install the wired controller when it is powered on.
Please install the wired controller after wall painting; otherwise,
water, lime and sand may enter the wired controller.
3.2 Basic Parameters
Items
Rated voltage
Wiring size
Operating environment
Humidity
Description
DC18V
RVVP-0.75mm
-5°C ~ 43°C
≤ RH90%