C/K settings table: choose the value by your CT and 1
C/K
C.T.
50/5
60/5
80/5
100/5
150/5
200/5
250/5
300/5
400/5
500/5
600/5
800/5
PF setting
• • • •
After setting the C/K value, press the [SETUP] button again for 4 secs to indicate the selected PF required. At the
same the red led's "Ind" and "Cap" will lighting. Release the "SETUP" button and use the [
change the selection. A P.F. of 0.95 is recommended.
SAVE THE SETTINGS
By pressing the [SETUP] button again the C/K, P.F. values which have been selected will be saved and the
Regulator works in AUTOMATIC condition.
Note – It is not necessary to set the rated frequency, the Power Factor Regulator auto-set the mains value.
ALARMS
REFERENCE
No supply voltage
Low P.F. value in the
network
Low voltage
High voltage
Zero Current
Low Current
High current
Leading P.F. value
Power loss
Manual forced banks Manual working selected
Other operation anomalies: please check again the correctness of the installation operations and check again all points of
"operation anomalies and remedies". A simple connection mistake can cause the P.F. Controller to function incorrectly. If the P.F.
Controller continues to work incorrectly, contact the Technical Office of the COMAR CONDENSATORI S.p.A, referring to the serial
number of the equipment (visible on the aluminium plate) and the value of measured current on the secondary circuit of the C.T.
2,5
5
0,25
0,50
0,25
0,50
0,15
0,33
0,15
0,25
0.08
0,15
0,06
0,15
0,05
0,10
0,05
0,08
0,05
0,06
0,05
0,05
0,05
0,05
0,05
0,05
On 220/240 VAC networks the C/K value must be doubled
The "-" symbol means a C.T. value too small (not acceptable)
CONDITION
V < 70% Un
All banks connected
PF = IND for 15 '.
V < 0,9 Un per 10 sec.
V > 1,1 Un per 10 sec.
A < 50 mA RMS
for 10 secs.
A < 350 mA RMS
for 10 secs.
A > 5.5A RMS
for 10 secs.
-0,20< PF <0,20 for 10"s
V < 200 volt for 200 ms
by the operator
13
st
bank reactive power
1st Capacitor Bank Power Value in kvar (C)
6
10
12,5
0,50
1,00
0,50
1,00
1.00
0,33
0,50
1,00
0,33
0,50
0,50
0,25
0,33
0,50
0,15
0,25
0,33
0,15
0,25
0,25
0,10
0,15
0,25
0,08
0,15
0,15
0,06
0,10
0,15
0,05
0,08
0,10
0,05
0,06
0,08
DISPLAY INDICATIONS
Display off
Ind blinking
LoU blinking
HiU blinking
A=0 blinking
LOA blinking
HIA blinking
CAP blinking
GA4 or pinpoint blinking
Manual-button LED illuminated Banks insertion controlled by the
20
25
-
-
-
-
-
-
1,00
-
0,50
1,00
0,50
0,50
0,50
0,50
0,33
0,50
0,25
0,33
0,25
0,25
0,15
0,25
0,15
0,15
+
SITUATION
All outputs off
All outputs on
Quick switch off for all outputs
Quick switch off for all outputs
Quick switch off for all outputs
(Automatic working only)
Inhibit output switch on
---
Quick switch off for all outputs
Switch off all outputs and re-start
operator (no AUTO)
MU02.06 MMM REV.5 11/05
-
] or [
] buttons to
loading