Transformador D/D0° Con Falla En Fase B A C En El Devanado Delta Secundario - GE T60 Manual De Instrucciones

Relè para proteccion de transformador
Tabla de contenido
8 ARRANQUE
TRANSFORMADOR D/D0° CON FALLA EN FASE B A C EN EL DEVANADO DELTA SECUNDARIO
Transformador: D/D0°, 20 MVA, 115/12.47 kV, TC1 (200:1), TC2 (1000:1)
I (f) = 0
A
A
I (f) = 0.866 pu –90°
B
B
C
I (f) = 0.866 pu –270°.
C
Figura 8–5: CORRIENTE DE TRANSFORMADOR D/D CON FALLA «A» HACIA «B» EN EL LADO DE BAJA
PRUEBA
FASE
CORRIENTE INYECTADA
CORRIENTE D1
Condición
A
balanceada
0.435 ∠–90°
B
0.435 ∠–270°
C
Arranque
A
mínimo
0.09 ∠–90°
B
0.09 ∠–270°
C
Arranque
A
mínimo
0.21 ∠–90°
B
0.21 ∠–270°
C
Pendiente 1
A
0.651 ∠–90°
B
0.651 ∠–270°
C
Pendiente 1
A
0.63 ∠–90°
B
0.63 ∠–270°
C
Intermedio
A
entre
1.2 ∠–90°
B
pendiente
1 y 2
1.2 ∠–270°
C
Intermedio
A
entre
0.8 ∠–90°
B
pendiente
1 y 2
0.8 ∠–270°
C
Pendiente 2
A
0.315 ∠–90°
B
0.315 ∠–270°
C
Pendiente 2
A
0.18 ∠–90°
B
0.18 ∠–270°
C
GE Multilin
8.2 EJEMPLOS DE PRUEBA DE LA CARACTERÍSTICA DIFERENCIAL
D/d0° Transformer
H winding
CORRIENTE D2
0 ∠0°
0 ∠0°
0.8 ∠–270°
0.8 ∠–90°
0 ∠0°
0 ∠0°
0.23 ∠–270°
0.23 ∠–90°
0 ∠0°
0 ∠0°
0.486 ∠–270°
0.486 ∠–90°
0 ∠0°
0 ∠0°
1.39 ∠–270°
1.39 ∠–90°
0 ∠0°
0 ∠0°
1.39 ∠–270°
1.39 ∠–90°
0 ∠0°
0 ∠0°
4.63 ∠–270°
4.63 ∠–90°
0 ∠0°
0 ∠0°
4.63 ∠–270°
4.63 ∠–90°
0 ∠0°
0 ∠0°
8.33 ∠–270°
8.33 ∠–90°
0 ∠0°
0 ∠0°
8.33 ∠–270°
8.33 ∠–90°
T60 relé para protección de transformador
8.2.5 EJEMPLO DE PRUEBA 4
X winding
I (f) = 0.866 pu –90°
b
I (f) = 0.866 pu –270°
c
CORRIENTE MOSTRADA
DIFERENCIAL
RESTRICCIÓN
0 ∠0°
0 ∠0°
0 ∠0°
0.8 ∠–270°
0 ∠0°
0.8 ∠–90°
0 ∠0°
0 ∠0°
0.065 ∠0°
0.230 ∠–270°
0.065 ∠0°
0.230 ∠–90°
0 ∠0°
0 ∠0°
0.102 ∠0°
0.486 ∠–270°
0.101 ∠0°
0.486 ∠–90°
0 ∠0°
0 ∠0°
0.195 ∠0°
1.39 ∠–270°
0.195 ∠0°
1.39 ∠–90°
0 ∠0°
0 ∠0°
0.233 ∠0°
1.39 ∠–270°
0.233 ∠0°
1.39 ∠–90°
0 ∠0°
0 ∠0°
2.44 ∠–270°
4.63 ∠–270°
2.44 ∠–90°
4.63 ∠–90°
0 ∠0°
0 ∠0°
3.18 ∠–270°
4.63 ∠–270°
3.18 ∠–90°
4.63 ∠–90°
0 ∠0°
0 ∠0°
7.77 ∠–270°
8.33 ∠–270°
7.77 ∠–90°
8.33 ∠–90°
0 ∠0°
0 ∠0°
8 ∠–270°
8.33 ∠–270°
8 ∠–90°
8.33 ∠–90°
I (f) = 0
a
A
B
F
C
828739A1.CDR
ESTADO
No aplicable
Bloquea
I
= 0.065 < arranque
d
mínimo
Opera
I
= 0.101 > arranque
d
mínimo
Bloquea
I
I
/
= 14% < 15%
d
r
Opera
I
I
/
= 16.8% > 15%
d
r
Bloquea
I
I
/
= 52.6%
d
r
< 60%
computado
Opera
I
I
/
= 68.8%
d
r
> 60%
calculé
Bloquea
I
I
/
= 93.2%
d
r
< pend. 2 = 95%
Opera
I
I
/
= 96%
d
r
> pend. 2 = 95%