Ferroli BlueHelix HiTech RRT 24 C Instrucciones De Uso, Instalación Y Mantenimiento página 364

Idiomas disponibles
  • ES

Idiomas disponibles

Index Description
b15 Flowmeter type selection
b16 Not implemented
b17 Not implemented
b18 DHW mode activation flow rate
b19 DHW mode deactivation flow rate
b20 Flue material selection
b21 Not implemented
b22 Not implemented
Standard flue shutdown maximum tem-
b23
perature
PVC flue shutdown maximum tempera-
b24
ture
CPVC flue shutdown maximum tempera-
b25
ture
b26 Not implemented
Calibration procedure [AUTO
b27
SETUP]
b28 Not implemented
b29 Restore Factory Values
P30 Heating ramp
P31 Heating standby time
P32 Heating Post-Circulation
P33 Pump operation
P34 Pump modulation DeltaT
P35 Modulating pump min. speed
P36 Modulating pump start speed
P37 Modulating pump max. speed
Pump deactivation temperature during
P38
Post-Circulation
Pump activation hysteresis temperature
P39
during Post-Circulation
P40 Heating user max. setpoint
P41 Max. output in heating
P42 Burner shutdown in DHW
P43 Comfort mode activation temperature
P44 Comfort mode deactivation hysteresis
P45 DHW standby time
P46 DHW user max. setpoint
P47 DHW pump Post-Circulation
364
BlueHelix HiTech RRT C
Range
1 = Flow. (450 imp/l)
2 = Flow. (700 imp/l)
3 = Flow. (190 imp/l)
--
--
15 - 100l/min/10 (do not set this value below 16)
15 - 100 l/min/10
0 = Standard
1 = PVC
2 = CPVC
--
--
60-110°C
60-110°C
60-110°C
--
5 = Calibration procedure [AUTO SETUP] enabled
All other values = Calibration procedure [AUTO SETUP] disa-
bled
(See "Calibration procedure [AUTO SETUP]" on
page 361)
--
See "* Restore Factory Values" on page 365.
10÷80
(ex. 10=20°C/min, 20=12°C/min, 40=6°C/min, 80=3°C/min)
0 - 10 minutes
0 - 255
(Multiply the value by 10. Example 15 x 10 = 150
seconds)
0 = Continuous pump (active only in winter mode)
1 = Modulating pump
0 - 40°C
30 - 100 %
30 - 100 %
50 - 100 %
0 - 100°C
0 - 100°C
20 - 90°C
0 - 100%
0 = Fixed
1 = Linked to setpoint
2 = Solar
0 - 80°C
0 - 20°C
30 - 255 seconds
40 - 65°C
0 - 255 seconds
cod. 3541V304 - Rev. 00 - 03/2024
Default
3
--
--
25
20
0
--
--
105
93
98
--
0
--
0
40
4
15
1
20
40
90
100
55
25
80
24 kW = 80
28 kW = 85
34 kW = 90
0
40
20
120
55
30
EN