7. Test the signal strength between the sounder and the
expander module. Single press the ENROLL button and wait
for the operation LED indication:
- 3 flashes in green - excellent signal strength;
- 3 flashes in orange - good signal strength, but, if possible,
change the place of installation;
- 3 flashes in red - poor signal strength and it is obligatory to
change the place of installation.
You can also check the signal quality for the device in DEVICE
RSSI menu of the module - item 8.
8. If the signal quality and strength are excellent or good, you
can proceed with mounting.
9. Use appropriate fixing elements to mount the wireless fire
base to the place of installation. Follow the instructions in item
3 to lock the sounder to the fire base if this is needed.
10. Place the sounder in the base as observe the two short
marks to coincide. Move the sounder's body up to hide the
marks. Rotate the sounder on clock side until a click is heard.
7. Reset of the Sounder
If the sounder is not new, you have to reset it before enrolment
to the expander module. Check the batteries condition. It is
recommended to change all of them with a brand new.
To reset the 45SCI100, power it on with the batteries and after
that press and hold ENROLL button for 5-7 seconds. The reset
is complete when the operation LED flashes 3 times in green,
followed from 1 long flash in red and 1 long flash in green.
Next pressing of ENROLL button will start the enrolment
procedure to expander module.
8. Checking the Signal Quality (RSSI)
The quality of the signal between the sounder and the
expander module is checked at DEVICE RSSI menu of the
module. The signal quality is assessed in [dB].
1. Enter in programming mode of the module. Scroll to menu
DEVICE RSSI and press ENTER button. A list with present
enrolled devices is shown on the screen with an order number
and type of the device.
2. Find in the list the sounder number.
3. Press ENTER button. Refer to the table below to read the
signal quality on the screen:
SIGNAL QUALITY LEVEL RSSI
< -90 dB
Loss
-90 ÷ -70 dB
Good
> -70 dB
Excellent
4. You can exit the menu at any time with pressing CANCEL
button.
9. Finding the Sounder Installation Place
and Test
This is a procedure that helps the engineer to find the exact
location of every wireless device in the fire installation and test
the connection with module.
1. Enter in programming mode of the module. Scroll to menu
FIND DEVICE and press ENTER button. A list with present
enrolled devices is shown on the screen with an order number
and type of the device.
2. Find in the list the sounder number which you want to locate
in the fire installation.
3. Press ENTER button. Message FINDING >>> (arrows are
blinking) appears on the screen showing that the module is
8
DESCRIPTION
Bad signal or no connection.
The signal is satisfactory but needs
improvement. It is recommended
to change the installation place of
the device.
Excellent signal.
scanning for signals from the selected wireless device. The
message will change for a while to FINDING DONE in case of
success.
4. The sounder will respond with active strobe and short
sound signals.
5. The module will exit automatically the finding procedure
after 70-80 seconds. You can also stop the procedure at any
time with pressing CANCEL button.
10. Replacing Batteries
It is recommended to change the batteries after 8 years
of operation regardless of their indicated discharge level.
Always use only batteries approved by the manufacturer -
Panasonic CR123A 3V or other with similar characteristics.
Attention: After indication from the panel/expander module
for low battery of a device, the user/ installer must replace
the discharged batteries with new within one month. The
remaining shelf time of the new batteries must not be less
than 6 years.
1. Disable the sounder operation to avoid fault messages.
2. Disassemble the sounder as described in item 3.
3. Remove the old batteries and place the new as observe the
+/- polarity.
4. Assemble the sounder back in place.
5. Enable the sounder operation.
6. Check the signal quality in DEVICE RSSI menu of the
expander module.
7. Test the sounder operability.
CAUTION: Do not expose used batteries to fire, hot ovens,
or mechanical crushing/cutting as this can result in an
explosion. Exposing batteries to extremely high environmental
temperatures or low air pressure can result in explosion or the
leakage of flammable liquid or gas.
DISPOSAL: Follow local regulations regarding disposal of the
batteries.
loading