3. Installation Place and Mounting
See figure 5 on page 3
4. PCB Elements
The PCB of 45SCI100 is factory mounted and is accessible
after disassembling the sounder from the wireless fire base –
see item 3.
1
CR123A 3V
CR123A 3V
CR123A 3V
2
1. Enroll button. The button is used for the following actions:
- Enrolling the sounder to the expander module.
- Checking the signal strength.
- Reset the sounder.
2. Power Batteries CR123A 3V
Attention: Use only batteries from the same type!
3. Bi-color operation LED (green/red). The LED is used for
following the actions during enrollment, reset and checking
the signal strength.
4. Tamper switch
5. Description of Tone Types
45SCI100 supports 32 different alarm tone types. The tone
type is set from the programming menus of the expander
module (conventional fire alarm systems) or programming the
sounders mode in the menus of the addressable fire alarm
panel. The sound volume level varies with the tone type
selected.
The main tone type of 45SCI100 is 27.
3
CR123A 3V
4
Tone
Tone Type
Toni
Tipi di toni
Geluid
Type
Tono
Tipo
Tonalité
1
2
3
4
5
6
554Hz, 0.1s/ 440Hz, 0.4s (AFNOR NF S 32 001)
7
500 - 1200Hz, 3.5s/ 0.5s OFF (NEN 2575:2000)
8
500 - 1200Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF
9
10
970Hz, 0.5s ON/0.5s OFF x 3/ 1.5s OFF (ISO
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
6. Enrolling to Expander Module
1. Remove the wireless fire base to access the PCB with the
batteries compartment. If the device is not new, perform reset
as described in item 7.
2. Enter in programming mode of the Comelit expander
module. Select ADD DEVICE menu and press ENTER button.
A list with already enrolled devices is shown on the screen
with an order number and type of the device.
3. Scroll down to find a free address to enroll the sounder.
Every free address is labeled as EMPTY.
4. Press ENTER button. Message SEARCHING >>> (arrows
are blinking) appears on the screen showing that the module
is scanning for signals from a wireless device in its covering
range.
Note: If there is no signal from the device in 2-minute period,
the expander module will exit automatically the programming
mode.
5. Power on the sounder - remove the protective folio from the
batteries if it is new - and single press the ENROLL button.
The operation LED (item 4, position 3) starts flashing in red.
6. In case of successful enrolment, the operation LED flashes
3 times in green and message DONE appears for a while on
the screen of the module. The sounder is added to the list as
45SCI100 type.
Tone Description
Descrizioni dei toni
Beschrijving
Descripción
970Hz
800Hz/970Hz @ 2Hz
800Hz - 970Hz @ 1Hz
970Hz 1s OFF/1s ON
970Hz, 0.5s/ 630Hz, 0.5s
420Hz 0.625s ON/0.625s OFF
(Australia AS1670 Alert tone)
(AS1670 Evacuation)
550Hz/440Hz @ 0.5Hz
8201)
2850Hz, 0.5s ON/0.5s OFF x 3/1.5s OFF
(ISO 8201)
1200Hz - 500Hz @ 1Hz (DIN 33 404)
400Hz
550Hz, 0.7s/1000Hz, 0.33s
1500Hz - 2700Hz @ 3Hz
750Hz
2400Hz
660Hz
660Hz 1.8s ON/1.8s OFF
660Hz 0.15s ON/0.15s OFF
510Hz, 0.25s/ 610Hz, 0.25s
800/1000Hz 0.5s each (1Hz)
250Hz - 1200Hz @ 12Hz
500Hz - 1200Hz @ 0.33Hz
2400Hz - 2900Hz @ 9Hz
2400Hz - 2900Hz @ 3Hz
(2500Hz - main sound frequency)
800Hz - 970Hz @ 100Hz
800Hz - 970Hz @ 9Hz
800Hz - 970Hz @ 3Hz
800Hz, 0.25s ON/1s OFF
600Hz - 1100Hz, 2.6s/0.4s OFF