Functional Characteristics; Reference Conditions; Metrological Properties; Voltage Detection - Chauvin Arnoux C.A 6460 Manual De Instrucciones

Óhmetro de tierra y deresistividad
Ocultar thumbs Ver también para C.A 6460:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

4. FUNCTIONAL CHARACTERISTICS

4.1

Reference conditions

Influence quantities
Temperature
Relative humidity
Supply voltage
Auxiliary resistances RH, RS, RES and RE
Spurious voltages (Ac and DC)
Serial inductances
Electrical field
Magnetic field
4.2

Metrological properties

4.2.1

Voltage detection

Measurement range: 20 to 250 V
terminals or between the S and E terminals.
Frequency: DC at 450 Hz
4.2.2

Resistance

Measurement range: 0 to 2000 Ω
Rating (Ω)
Resolution (Ω)
Intrinsic error
Measuring current
No load voltage
Response time: 4 to 8 seconds
When the unit is locked on the second rating, the
characteristics are as follows:
Rating (Ω)
Resolution
Intrinsic error
Measuring current
No load voltage
0.00 - 19.99
0.01
±2% ±1 pt
10 mA
27
Reference values
23°C ±3 K
45 to 55% HR
9.5 V ±0.2 V
< 1 V/m
< 40 A/m
between the H and E
AC
20.0 - 199.9
0.1
±2% ± 1pt
2% typical 5% max
1 mA
≤ 42 Vpeak
0.0 – 199.9
0.1 Ω
±2% ±1 pt
1 mA
≤ 42 Vpeak
zero
zero
zero
200 - 1999
1
±3 pt
0.1 mA
Tabla de contenido
loading

Este manual también es adecuado para:

C.a 6462P01126502P01126501

Tabla de contenido