MESSAGES
Calibration ongoing, therefore, avoid, as far as possible, opening the cold room
during the process. For further information, see page 27.
Flashing with temperature: Configuration has been changed from 1 to 2 evapora-
tors or vice versa.
SELFDRIVE MODE ALERT MESSAGES (Only shown pressing the Q key)
Defrost end error in 1/2 evaporator during the calibration, defrost has not ended due
to temperature.
Error during calibration in 1/2 evaporator. There is not enough difference in temperatu-
re between the cold room probe and the evaporator probe.
It has not been possible to carry out the calibration due to a lack of stability in the
system (Excessive door opening, excessive oscillations in the lower pressure, etc.).
Error during normal operation (SELFDRIVE Mode active) in 1/2 evaporator. There is not
enough difference in temperature between the cold room probe and the evaporator
probe.
A lack of stability has been detected in the system (Excessive door opening, excessi-
ve oscillations in the low pressure, etc.) during normal operation (SELFDRIVE Mode
active).
The persistent lack of stability has led to the deactivation of the SELFDRIVE mode.
Excessive door openings have been detected during calibration and it has not been
possible to calibrate.
Excessive door openings have been detected and the device cannot regulate in SEL-
FDRIVE mode.