Pentair 368 Manual De Instrucciones página 13

Ocultar thumbs Ver también para 368:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 42
Programming - 368/606
Calendar Override Setting
The model 606 demand control needs a method to set days between regeneration for regulatory require-
ments and for cases when the flow sensor has failed.
Enter by holding and for 3 seconds. The programmed calendar override is displayed. Press to
increase value.
Values the same as 604.
0 = no calendar override
0.3 = Regeneration every 8 hours
0.5 = Regeneration every 12 hours
1-30 days between regeneration
Default: 0
NOTE: During programming if a button is not pushed for 5 seconds, the control returns to the
normal operation mode and displays the Time of Day.
Pentair Residential Filtration, LLC
Time of Day: Press until desired hour appears. Release.
Range: 0 through 23 hours
Note: T he elapsed minutes will reset to zero when the hours are
changed.
Regenerant Dosage: Press until desired regenerant dosage
Range: 0.20 kg to 6.0 kg
0 .20 kg to 1.0 kg by increments of 0.05 kg
1 .0 kg to 3.0 kg by increments of 0.1 kg
3 .0 kg to 60 kg by increments of 0.5 kg
Default: 0.6kg
Capacity Cubic Meters: Press until desired interval appears.
Range: 0.40 to 9.5 cubic meters
0.4 m
to 1.0 m
3
1.0 m
to 3.0 m
3
3.0 m
to 5.0 m
3
5.0 m
to 9.5 m
3
368/606 PROGRAMMING IS COMPLETE
appears. Release.
Release.
by increments of 0.05 m
(12 increments)
3
3
by increments of 0.1 m
(20 increments)
3
3
by increments of 0.2 m
(10 increments)
3
3
by increments of 0.5 m
(10 increments)
3
3
13
Rev B

Hide quick links:

Tabla de contenido

Solución de problemas

loading

Tabla de contenido