and the compressor still operating will cause air or other gas to be
sucked in, raising the pressure inside the refrigeration cycle to an
abnormally high level, and possibly resulting in rupture, injury or
other trouble.
• Do not recover the refrigerant into the outdoor unit. Use a
refrigerant recovery machine to recover the refrigerant after
moving or repairing. It is impossible to recover the refrigerant into
the outdoor unit. Refrigerant recovery into the outdoor unit may
result in serious accidents such as explosion of the unit, injury or
other accidents.
CAUTION
R410A refrigerant air conditioner installation
• This air conditioner adopts the HFC refrigerant (R410A)
which does not destroy ozone layer.
• The characteristics of R410A refrigerant are; easy to absorb
water, oxidizing membrane or oil, and its pressure is approx. 1.6
times higher than that of refrigerant R22. Accompanied with the
R410A refrigerant, refrigerating oil has also been changed.
Therefore, during installation work, be sure that water, dust,
former refrigerant, or refrigerating oil does not enter the
refrigerating cycle.
• To prevent charging an incorrect refrigerant and refrigerating oil,
the sizes of connecting sections of charging port of the main unit
and installation tools are changed from those for the conventional
refrigerant.
• Accordingly the exclusive tools are required for the R410A
refrigerant.
• For connecting pipes, use new and clean piping designed for
R410A, and please care so that water or dust does not enter.
Do not wash air conditioners with pressure washers.
• Electric leaks may cause electric shocks or fi res.
7-EN
2
Accessory parts
Part name
Q'ty
Owner's Manual
1
Installation Manual
1
Binding band
6
– 4 –
Shape
Usage
(Be sure to hand over to customers)
(Be sure to hand over to customers)
For all models