Coupling size of brazed pipe
Connected section
External size
Internal size
G
K
Standard
External size
outer dia.
Standard outer dia.
of connected
(Allowable difference)
copper pipe
C
in
mm
in
mm
1/4
6.35
1/4"(±0.0012)
6.35(±0.03)
0.25" (
3/8
9.52
3/8"(±0.0012)
9.52(±0.03)
0.38" (
1/2
12.7
1/2"(±0.0012) 12.70(±0.03)
0.5" (
5/8
15.88 5/8"(±0.0012) 15.88(±0.03)
0.63" (
3/4
0.76" (
19.05 3/4"(±0.0012) 19.05(±0.03)
7/8
22.2
7/8"(±0.0012) 22.22(±0.03)
0.88" (
1-1/8
28.58
1-1/8"(±0.0012) 28.58(±0.04) 1.13" (
1-3/8
1-3/8"(±0.0012) 34.90(±0.04) 1.38" (
34.92
1-5/8
41.28
1-5/8"(±0.0012) 41.28(±0.05) 1.63" (
Selection of pipe materials and sizes
Selection of pipe materials
Materials : Phosphorus deoxidation seam-less pipe. Minimum wall thickness for R410A application.
Soft
Half hard or hard
21-EN
Connected section
Internal size
Min. depth of
insertion
Oval value
F
K
G
in
mm
in mm in mm
in
) 6.45 (
) 0.28
7
0.24
6
0.0024" or less 0.06 or less 0.020" 0.50
+0.0016
+0.04
0.0008
0.02
+0.0016
) 9.62 (
+0.04
) 0.31
8
0.28
7
0.0031" or less 0.08 or less 0.024" 0.60
0.0008
0.02
+0.0016
) 12.81 (
+0.04
) 0.35
9
0.31
8
0.0039" or less 0.10 or less 0.028" 0.70
0.0008
0.02
) 0.35
9
0.31
8
0.0051" or less 0.13 or less 0.031" 0.80
+0.0016
) 16.00 (
+0.04
0.0008
0.02
) 19.19 (
) 0.43 11 0.39 10 0.0059" or less 0.15 or less 0.031" 0.80
+0.0012
+0.03
0.0012
0.03
+0.0012
) 23.36 (
+0.03
) 0.43 11 0.39 10 0.0063" or less 0.16 or less 0.032" 0.82
0.0012
0.03
+0.0024
) 28.75 (
+0.06
) 0.51 13 0.47 12 0.0079" or less 0.20 or less 0.039" 1.00
0.0008
0.02
) 0.55 14 0.51 13 0.0098" or less 0.25 or less 0.047" 1.20
+0.0016
) 35.11 (
+0.04
0.0016
0.04
) 42.28 (
) 0.59 15 0.55 14 0.0110" or less 0.28 or less 0.053" 1.35
+0.0031
+0.08
0.0008
0.02
OD (in)
OD (mm)
1/4
6.35
3/8
9.52
1/2
12.70
5/8
15.88
3/4
19.05
7/8
22.22
1-1/8
28.58
1-3/8
34.92
1-5/8
41.28
– 11 –
Capacity code of indoor and outdoor units
For the indoor unit, the capacity code is decided at each capacity rank. (Table 1)
The capacity codes of the outdoor units are decided at each capacity rank. The maximum number of connectable
indoor units and the total value of capacity codes of the indoor units are also decided. (Table 2-1, Table 2-2)
NOTE
Compared with the capacity code of the outdoor unit, the total value of capacity codes of the connectable
indoor units differs based on the height difference between the indoor units.
When the height difference between the indoor units is 49 ft (15 m) or less: Up to 200% of the capacity code
of the outdoor unit.
When the height difference between the indoor units is over 49 ft (15 m): Up to 105% of the capacity code.
If the system diversity is more than 135%, check the maximum number of indoor unit connections in table 2-2.
Min.
thickness
Table 1
of
coupling
Indoor unit capacity type
mm
in
mm
0
0
7
0
0
9
0
1
2
0
1
5
0
1
8
0
2
1
0
2
4
0
2
7
0
3
0
0
3
6
0
4
2
0
4
8
0
5
4
0
7
2
0
9
6
120 type
* For combination of the outdoor units, refer to "Combination of outdoor units".
Minimum wall
thickness in (mm)
0.031" (0.80)
0.031" (0.80)
0.031" (0.80)
0.039" (1.0)
0.039" (1.0)
0.039" (1.0)
0.039" (1.0)
0.047" (1.2)
0.057" (1.45)
Indoor capacity code
(Equivalent to capacity)
y t
p
e
7
5 .
y t
p
e
9
5 .
y t
p
e
1
2
y t
p
e
1
5
4 .
y t
p
e
1
8
y t
p
e
2
1
y t
p
e
2
4
y t
p
e
2
7
y t
p
e
3
0
y t
p
e
3
6
y t
p
e
4
2
y t
p
e
4
8
y t
p
e
5
4
y t
p
e
7
2
y t
p
e
9
6
120
22-EN