Flow Selector unit address setting
■
On this unit, it is required to set the addresses of Flow selector units before starting air conditioning.
Set the addresses following below procedure.
■
Before Flow Selector unit address settings
Complete "Indoor unit address setting" and "TU2C-LINK communication setting".
Confi rm the schematic of piping and wiring.
CAUTION
Set only the Code (DN) number shown in the following table: DO NOT set any other Code (DN) number.
If a Code (DN) number not listed is set, it may not be possible to operate the air conditioner or other trouble with the
product may result.
Remote control model name: RBC-AWSU52-UL
▼ The method to change the address of an individual indoor unit (the indoor unit is paired with a
wired remote controller one to one), or an indoor unit in a group.
(The method is available when the addresses have already been set automatically.)
Field setting menu (2/3)
6.Setting louver position
7.Setting timer operation mode
8.Easy I.DN setting
9.DN Setting
9.DN setting
10.Reset Power Consumption data
61-EN
1
Push [
Menu] to open the "Menu"
2
Push and hold [
Menu] and [
] at the
same time to open "Field setting menu"
Push and hold 4 seconds.
3
In the "Field setting menu" screen, push
[
] and [
] to select "DN setting", and
then push [
Set/Fix]
4
Push [
] and [
] to select "Indoor
unit", and the push [
Set/Fix]
"Indoor unit" was selected, the fans and louvres
of the indoor units operate.
When doing group connections:
The fans and louvres of the selected indoor
units operate.
– 31 –
00FE
00FE
5
Push [
] to black highlight the code (DN),
and then push [
] and [
] to set the
code number to [00FE], [0105], [0106]
6
Push [
] to black highlight the data, and
then push [
] and [
] to set the data
7
After finishing setting the data of the code
(DN), push [
Set/Fix]
"Continue?" is displayed.
8
To set the data of other codes (DN), push
[
Set/Fix]
To not do other settings, push [
Return]
The changes are fixed, and the "Field setting
menu" screen returns.
" " appears while data is changing.
When doing group connections:
Push [
Return] to open the unit selection
screen. In the unit selection screen, push
[
Return] to briefly display " " , and then
return to the "Field setting menu" screen.
9
To change settings of another indoor unit,
repeat from Procedure 1.
62-EN