Flow Selector unit address setting
On this unit, it is required to set the addresses of Flow selector units before starting air conditioning.
Set the addresses following below procedure.
Before Flow Selector unit address settings
Complete "Indoor unit address setting" and "TU2C-LINK communication setting".
Confi rm the schematic of piping and wiring.
CAUTION
Set only the Code (DN) number shown in the following table: DO NOT set any other Code (DN) number.
If a Code (DN) number not listed is set, it may not be possible to operate the air conditioner or other trouble with the
product may result.
Remote control model name: RBC-AWSU52-UL
▼ The method to change the address of an individual indoor unit (the indoor unit is paired with a
wired remote controller one to one), or an indoor unit in a group.
(The method is available when the addresses have already been set automatically.)
Field setting menu (2/3)
6.Setting louver position
7.Setting timer operation mode
8.Easy I.DN setting
9.DN Setting
9.DN setting
10.Reset Power Consumption data
61-EN
1
Push [ 
Menu] to open the "Menu"
2
Push and hold [ 
Menu] and [ 
 ] at the
same time to open "Field setting menu"
Push and hold 4 seconds.
3
In the "Field setting menu" screen, push
[ 
 ] and [ 
 ] to select "DN setting", and
then push [ 
Set/Fix]
4
Push [ 
 ] and [ 
 ] to select "Indoor
unit", and the push [ 
Set/Fix]
"Indoor unit" was selected, the fans and louvres
of the indoor units operate.
When doing group connections:
The fans and louvres of the selected indoor
units operate.
– 31 –
00FE
00FE
5
Push [ 
 ] to black highlight the code (DN),
and then push [ 
 ] and [ 
 ] to set the
code number to [00FE], [0105], [0106]
6
Push [ 
 ] to black highlight the data, and
then push [ 
 ] and [ 
 ] to set the data
7
After finishing setting the data of the code
(DN), push [ 
Set/Fix]
"Continue?" is displayed.
8
To set the data of other codes (DN), push
[ 
Set/Fix]
To not do other settings, push [ 
Return]
The changes are fixed, and the "Field setting
menu" screen returns.
"    " appears while data is changing.
When doing group connections:
 Push [ 
Return] to open the unit selection
screen. In the unit selection screen, push
[ 
Return] to briefly display "    " , and then
return to the "Field setting menu" screen.
9
To change settings of another indoor unit,
repeat from Procedure 1.
62-EN