 DN setting
Remote controller model name: RBC-AWSUS*-UL
Basic procedure
Be sure to stop the air conditioner before making settings.
(Change the setup while the air conditioner is not working.)
CAUTION
Set only the Code No. shown in the following table: Do NOT set any other Code No.
If a Code No. not listed is set, it may not be possible to operate the air conditioner or other trouble with the product
may result.
1
In the "Field setting menu" screen, press [
2
Press [
] and [
] to select "Indoor unit" or "Outdoor unit", and the press [
If "Indoor unit" was selected, the fans and louvers of the indoor units operate.
When doing group connections:
The fans and louvers of the selected indoor units operate.
3
Press [
] to black highlight the item code (DN), and then press [
4
Press [
] to black highlight the data, and then press [
5
After finishing setting the data of the item code (DN), press [
"Continue?" is displayed.
6
To set the data of other item codes (DN), press [
The changes are fixed, and the "Field setting menu" screen returns.
" " appears while data is changing.
When doing group connections:
Press [
Return] to open the unit selection screen. In the unit selection screen, press [
display " ", and then return to the "Field setting menu" screen.
] and [
] to select "DN setting", and then press [
] and [
] and [
] to set the data
Set/Fix]
Set/Fix] To not do other settings, press [
– 36 –
Set/Fix]
Set/ Fix]
] to set the item code
Return]
Return] to briefly