INFOSEC UPS SYSTEM E6 LCD RT Evolution 5 KVA Guía De Usuario página 18

Ocultar thumbs Ver también para E6 LCD RT Evolution 5 KVA:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

3) Output setting (only available or effective on bypass mode)
Interface
4) Battery setting (available on all operation modes)
Interface
18
Description
1.
Volt:
208: Presenting the rated output voltage with 208Vac
220: Presenting the rated output voltage with 220Vac
230: Presenting the rated output voltage with 230Vac
240: Presenting the rated output voltage with 240Vac
2.
Freq:
50Hz: The output frequency is setting for 50Hz.
60Hz: The output frequency is setting for 60Hz.
ATO: If selected, output frequency will be decided according
to the latest normal utility frequency. If it is from 46Hz to
54Hz, the output frequency will be 50.0Hz. If it is from 56Hz
to 64Hz, the output frequency will be 60.0Hz. ATO is default
setting.
3.
CVCF:
Enable or disable converter mode.
Enable: The output frequency will be fixed at 50Hz or 60Hz
according to setting of "Freq". The input frequency could be
from 46Hz to 64Hz.
Disable: The output frequency will synchronize with the
input frequency within 46~54 Hz for 50Hz system or within
56~64 Hz for 60Hz system.
NOTE: CVCF means Constant Voltage and Constant
Frequency, it represents converter mode.
Description
1.
Dischg Protect:
1.1
Enable: Battery discharge protection function is enabled. When
UPS have been continuously working in "battery/battery test
mode", the UPS will automatically shut down when the running
time set by option 1.2 below is up;
Disable: Battery discharge protection function is disabled.
1.2
0000~1500: The maximum discharge time ranging from 0 to
1500mins. UPS will shut down to protect battery after backup
time arrives when the "Dischg Protect" is enabled. If "Dischg
protect" is disabled, then this setting does not make sense
whatever the setting is; The default value for this setting is
990mins.
2. Batt Test Type:
2.1 Short Time: Battery test will last for 10 seconds.
2.2 Long Time: Battery test could last for longer time, which is
able to be adjusted within 01~99 minutes.
2.3 Till Batt Low: Battery test will not stop until battery voltage
is low.
INFOSEC UPS SYSTEM - 4, rue de la Rigotière - 44700 Orvault - FRANCE - www.infosec-ups.com
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)2 40 94 29 51 - [email protected] – 05 13 AA 59 208 13
Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

E6 lcd rt evolution 6 kvaE6 lcd rt evolution 8 kvaE6 lcd rt evolution 10 kvaE6 lcd rt evolution 5 kva sE6 lcd rt evolution 6 kva sE6 lcd rt evolution 8 kva s ... Mostrar todo

Tabla de contenido