Annex A. Rated Parameters Set On Lcd - Temper 6KS Manual De Instrucciones

Sistema de alimentación ininterrumpida
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Annex A. Rated Parameters Set on LCD

1. Power on LCD
2. Press button
IP V(LN) 220
OP V(LN) 220
FREQ HZ 50
3. Press button "ENTER" to activate setting function as below. Shadow means the current
parameter can be set now.
IP
OP
FREQ HZ 50
4. Input voltage setting is activated. Press
voltages are available for customer such as: 110V, 120V, 127V, 200V, 208V, 220V, 230V, 240V.
5. Press "ENTER" button to confirm input voltage selection and activate output voltage setting
menu as below. Press
available for customer such as: 110V, 120V, 127V, 200V, 208V, 220V, 230V, 240V.
IP
OP
FREQ HZ 50
6. Press "ENTER" button to confirm output voltage selection and activate frequency setting.
Press
to select the rated frequency. 50Hz and 60Hz are available for selection.
together for 3 seconds, enters in rated setting menu as below
RATE SET
RATE SET
V(LN) 220
V(LN) 220
to select the rated input voltage. The
to select the rated output voltage. Output voltages are
RATE SET
V(LN) 230
V(LN) 220
True Online 6-20k UPSUserManual
Rated Parameters Seton LCD
230
220
50
230
230
50
157
Tabla de contenido
loading

Productos relacionados para Temper 6KS

Este manual también es adecuado para:

6kl10ks10kl15kl20kl

Tabla de contenido