Trouble Shooting

10. TROUBIE SHOOTING

This section describes checking the UPS's status. This section also indicates various UPS
symptoms a user may encounter and provides a troubleshooting guide in the event the UPS
develops a problem. Use the following information to determine whether external factors
caused the problem and how to remedy the situation.

10.1 Checking UPS status

It recommended that checking the UPS operation status every six months.
Check whether the UPS is faulty: Is the Fault Indicator on? Is the UPS sounding an
alarm?
Check whether the UPS is operating in Bypass mode. Normally, the UPS operates
in Normal Mode. If it is operating in Bypass Mode, stop and contact your local
representative, or Channel Support.
Check whether the battery is discharging. When the utility input is normal, the
battery should not discharge. If the UPS is operating in Battery Mode, stop and
contact your local representative, or Channel Support.

10.2 Adjust the factors caused the problem

When the fault indicator is on, press
and A0-A5 indicates the exact fault of UPS, S-code list is shown as follow:
Description of S-Code
Seq.
Items
Synchronous
1
1
Fault
2
2
Main Input Fault
3
3
REC Fault
A0
4
4
INV Fault
5
5
Reserved
6
6
Reserved
7
7
Reserved
8
8
Reserved
9
9
Reserved
152
True Online 6-20k UPSUserManual
button to get S-code. So,S1 indicates status
0
1
Solution
Not
Check
Sync
sync.
voltage/frequency is normal
OK
Fault
Check whether input is normal
REC over temperature, bus
OK
Fault
over
voltage,
unbalance, soft start fail
INV over temperature, INV
OK
Fault
IGBT broken, INV relay fault
whether
bypass
input
current