PRIOR MANUFACTURER CONFIGURATION
The unit must be configured as follows in order to function correctly:
1.
Advanced Configuration > Controller Type: (Unit) or (Unit + Room)
2.
Select the circuits controlled by the device: (C1), (C2) or (C1 + C2).
EN
3.
Configure the circuits to be used in Heating as "Fix". Indicate whether DHW is available.
4.
Configure the circuits to be used in Cooling as "Fix".
5.
Configure the "Central Mode" as "Full".
6.
Select "Wired" on the thermostats to be installed.
Note: A thermostat must always be associated to each circuit set to room temperature
to enable a temperature reading. The zone cannot be switched on or off through the room
thermostat.
Note: The unit may need to be restarted after performing the configuration.
In Cooling mode, supply temperatures must be set to a maximum of 22°C and a minimum of
5°C: System Configuration > Space Cooling > Circuit 1 > Working limits