Model
AK036HARDCC/VN
AK048HARDCC/VN
AK060HARDCC/VN
IFM - Indoor Fan Motor Tap
PURPLE
RED
BLACK
BLUE
CC
COMP
OFM
RC 1
RC 2
RC 3
GND
IFM
HPC
LPC
HGS
WARNING:
CABINET MUST BE PERMANENTLY
GROUNDED AND ALL WIRING TO CONFORM TO I . E . C , N . E . C , C . L . C , AND LOCAL CODES AS
APPLICABLE REPLACEMENT WIRE MUST BE THE SAME GAUGE AND INSULATION TYPE AS
ORIGINAL WIRE .
Note 1) Remove the red lead from "240 V" terminal and then connect the red lead to "208 V" terminal on the transformer for
208 volts .
Note 2) Exchange the indoor Fan motor red wire and blue wire for medium speed ; exchange the Fan motor black wire and
blue wire for high speed ; Default setting of the indoor Fan motor is 'low' .
Rooftop_ODM_IBIM_EN_2020001B8001.indd 35
"A"
250 V, T30 A
250 V, T50 A
250 V, T50 A
COM
MEDIUM
HIGH
LOW
COMPRESSOR CONTACTOR
COMPRESSOR
OUTDOOR FAN MOTOR
COMPRESSOR RUN CAPACITOR
OUTDOOR FAN MOTOR RUN CAPACITOR
INDOOR FAN MOTOR RUN CAPACITOR
GROUND CHASSIS
INDOOR FAN MOTOR
HIGH PRESSURE SWITCH
LOW PRESSURE SWITCH
HOT GAS SWITCH
ENGLISH-35