Federal Signal Global G-STR Instrucciones De Instalación Y Mantenimiento página 15

Ocultar thumbs Ver también para Global G-STR:
Idiomas disponibles

Idiomas disponibles

All manuals and user guides at all-guides.com
The maximum wire gauge is 2.5 mm
be rated 85 °C or higher. Use only stranded cable to terminate the
beacon. The cross-sectional area of the primary earth (ground) must
equal the cross-sectional area of the phase conductor.
Cable termination for these models should be in accordance with
specifications applying to the application. It is recommended that all
cables and cores should be fully identified. Use the appropriate cable
gland for the application. Gland entry threads are M20-1.5 x 6H.
Tools needed:
• 1.5 mm A/F hexagon key
• 2 mm flat-tip screwdriver
• No. 1 Phillips screwdriver
• Wire stripper
Wiring the Ex d Models
To wire the Ex d models:
1.
Unscrew the M3 hex set screw on the side of the housing one
full turn.
2.
Remove the lens cover from the housing by turning the cover
counter-clockwise. Three 120 degree spaced reliefs are provided
for a 3/8 in spanner wrench if needed. If the cover will not
unscrew, back out the set screw a few additional turns.
3.
Loosen the captive Phillips screw retaining the printed circuit
board (PCB).
4.
Slide out the PCB until the terminals clear the housing. Strip the
wire insulation 5 mm to 6 mm (0.22 in).
24 Vdc Models
a.
See Figure 10 on page 16. Connect the positive (+) power
source wire to the terminal-block screw marked + .
b. Connect the negative (
block screw marked
Model G-STR Global Series Strobe Beacon
Installation and Maintenance Instructions
(12 AWG). The wire must
2
) power source wire to the terminal
.
15
loading