Installation
3.2. Data available
The maximum numbers of units that can be controlled using HC-A16KNX are 16. Each unit has 15 communication objects. These
objects are explained as follows:
Address
Name
0
Unit-N On/Off
1
Unit-N Mode
2
Unit-N Fan
3
Unit-N Louver Scale
4
Unit-N Louver Auto
5
Unit-N Set Temperature
6
Unit-N Ambient Temperature
7
Unit-N Alarm
8
Unit-N Alarm Code
9
Unit-N Mode Cool
10
Unit-N Mode Dry
11
Unit-N Mode Fan
12
Unit-N Mode Heat
13
Unit-N Mode Auto
14
Unit-N Prohibit
?
Note:
Offset position is (N*15) + Address. Where N is the Indoor Unit position in the address table (0~15) and address is the position
of the register as shown in the table.
Address from 9 to 13 will work together. They are used to set the function mode. Only one of them could be activated at the
same time. When one of these bits will be set as 1, the rest will be changed at 0.
n
Global objects:
Address
Name
1~16
Unit-1~16
240
Communication
Alarm
Error code list:
n
Code (in Hexadecimal) Description
0
No Error
1~98
See Hitachi documentation
99
Unit not configured
Length
1 bit
ON / OFF order.
1 byte
Mode setting order.
1 byte
Fan setting order.
1 byte
Louver position setting.
1 bit
Automatic Louver Setting.
2 bytes
Setting temperature.
2 bytes
Intel Air Ambient Temperature
1 bit
Alarm notification.
1 byte
Alarm code.
1 bit
Cool mode order.
1 bit
Dry mode order.
1 bit
Fan mode order.
1 bit
Heat mode order.
1 bit
Auto mode order.
1 bit
On Yes works only with KNX orders, on
No, the unit could receive local orders
and from KNX too.
Length
Description
1 bit per unit
Shows if HC-A16KNX used the communication with the
H-LINK PCB for unit N where N is the address to read.
1 bit
With value is 1 means that is not possible to communicate
with the H-LINK PCB. On 0, communication is working
properly.
Description
PMML0193A rev.2 - 06/2010
Values
0-On
1-Off
0 = Auto
1 = Heat
2 = Dry
3 = Fan
4 = Cool
0~30%= Low
31~60%= Medium
61~100%= High
0~15% = Pos0
16~30% = Pos1
31~45% =Pos2
46~60% = Pos3
61~75% =Pos4
76~90% = Pos5
91~100% = Pos6
1 = Louver Automatic active
17~30ºC
17~30ºC
1 = alarm on unit N
See errors table from
HC-A16KNX
1 = Mode Cool Active
1 = Mode Dry Active
1 = Mode Fan Active
1 = Mode Heat Active
1 = Mode Auto Active
0 = No
1 = Yes
Values
1=Communication
works
1=Communication
Alarm.
13