Electrical Installation
E
N
G
L
I
S
H
Power Supply Unit
Must be located outside the AIVIA, never
installed inside the AIVIA.
• The power supply block must include:
- A 10A/30mA residual current device, serving
both to protect and disconnect the hardware.
- Safety Extra Low Voltage Wiring* or equivalent
24VDC +-2% / 3A Class II, and IEC 60950-1
conform.
- The cable connecting the residual current device
and the power supply must be a section of 15AWG
(1,5 mm²).
• The main connection must include the primary
phase, and neutral.
• The maximum full load secondary voltage drop
must not exceed 2%, or 23.5V at the AIVIA terminal.
• The power block must be dust and waterproof, and
ventilated**.
• Wires must be held against themselves by a
collar at the nearest of the holding terminals. The
power block wiring must conform to standards in
force in the country of use.
* Recommended power supply: Meanwell HDR100-
24 or DR100-24
** Natural or forced convection depending on the
environment and thermal characteristics at maximum
load.
Safety Extra Low Voltage Wiring
(SELV)
• Type U1000R2V. 2 insulated jacketed conductors,
15AWG (1.5 mm²) area, 33 feet (10 m) maximum
length.
• Use red or maroon color cable for the +24V line.
• Use black or gray color cable for the 0V line.