Coupling size of brazed pipe
Connected section
External size
Internal size
G
K
Standard
External size
Internal size
outer dia.
Standard outer dia.
of connected
(Allowable difference)
copper pipe
C
in
mm
in
mm
in
1/4
6.35
1/4"(±0.0012)
6.35(±0.03)
0.25" (
+0.0016
0.0008
3/8
9.52
3/8"(±0.0012)
9.52(±0.03)
0.38" (
+0.0016
0.0008
1/2
0.5" (
12.7
1/2"(±0.0012) 12.70(±0.03)
+0.0016
0.0008
5/8
15.88 5/8"(±0.0012) 15.88(±0.03)
0.63" (
+0.0016
0.0008
3/4
19.05 3/4"(±0.0012) 19.05(±0.03)
0.76" (
+0.0012
0.0012
7/8
22.2
7/8"(±0.0012) 22.22(±0.03)
0.88" (
+0.0012
0.0012
1-1/8
1-1/8"(±0.0012) 28.58(±0.04) 1.13" (
28.58
+0.0024
0.0008
1-3/8
34.92
1-3/8"(±0.0012) 34.90(±0.04) 1.38" (
+0.0016
0.0016
41.28
1-5/8
1-5/8"(±0.0012) 41.28(±0.05) 1.63" (
+0.0031
0.0008
Selection of pipe materials and sizes
Selection of pipe materials
Materials : Phosphorus deoxidation seam-less pipe. Minimum wall thickness for R410A application.
Soft
Half hard or hard
19-EN
Connected section
Min. depth of
insertion
Oval value
F
K
G
mm
in mm in mm
in
mm
) 6.45 (
) 0.28
7
0.24
6
0.0024" or less 0.06 or less 0.020" 0.50
+0.04
0.02
) 9.62 (
) 0.31
8
0.28
7
0.0031" or less 0.08 or less 0.024" 0.60
+0.04
0.02
) 12.81 (
) 0.35
9
0.31
8
0.0039" or less 0.10 or less 0.028" 0.70
+0.04
0.02
) 16.00 (
) 0.35
9
0.31
8
0.0051" or less 0.13 or less 0.031" 0.80
+0.04
0.02
) 0.43 11 0.39 10 0.0059" or less 0.15 or less 0.031" 0.80
) 19.19 (
+0.03
0.03
) 0.43 11 0.39 10 0.0063" or less 0.16 or less 0.032" 0.82
) 23.36 (
+0.03
0.03
) 0.51 13 0.47 12 0.0079" or less 0.20 or less 0.039" 1.00
) 28.75 (
+0.06
0.02
) 35.11 (
+0.04
) 0.55 14 0.51 13 0.0098" or less 0.25 or less 0.047" 1.20
0.04
) 42.28 (
+0.08
) 0.59 15 0.55 14 0.0110" or less 0.28 or less 0.053" 1.35
0.02
Minimum wall
OD (in)
OD (mm)
thickness in (mm)
1/4
6.35
0.031" (0.80)
3/8
9.52
0.031" (0.80)
1/2
12.70
0.031" (0.80)
5/8
15.88
0.039" (1.0)
3/4
19.05
0.039" (1.0)
7/8
22.22
0.039" (1.0)
1-1/8
28.58
0.039" (1.0)
1-3/8
34.92
0.047" (1.2)
1-5/8
41.28
0.057" (1.45)
Capacity code of indoor and outdoor units
For the indoor unit, the capacity code is decided at each capacity rank. (Table 1)
The capacity codes of the outdoor units are decided at each capacity rank. The maximum number of connectable
indoor units and the total value of capacity codes of the indoor units are also decided. (Table 2-1, Table 2-2)
NOTE
Compared with the capacity code of the outdoor unit, the total value of capacity codes of the connectable
indoor units differs based on the height difference between the indoor units.
When the height difference between the indoor units is 49 ft (15 m) or less: Up to 200% of the capacity code
(Equivalent to HP) of the outdoor unit.
When the height difference between the indoor units is over 49 ft (15 m): Up to 105% of the capacity code.
If MMU-UP
H is include in the system, total indoor capacity code must be between 50% and 105% of
outdoor unit capacity.
Min.
thickness
If the system diversity is more than 135%, check the maximum number of indoor unit connections in table 2-1,
of
2-2, and then turn on DIP switch 3 of SW103 on the interface P.C. boards.
coupling
Table 1
in
mm
Indoor unit capacity type
0
0
7
y t
p
e
0
0
9
y t
p
e
0
1
2
y t
p
e
0
1
5
y t
p
e
0
1
8
y t
p
e
0
2
1
y t
p
e
0
2
4
y t
p
e
0
2
7
y t
p
e
0
3
0
y t
p
e
0
3
6
y t
p
e
0
4
2
y t
p
e
0
4
8
y t
p
e
0
5
4
y t
p
e
0
7
2
y t
p
e
0
9
6
y t
p
e
120 type
* For combination of the outdoor units, refer to "Combination of outdoor units".
– 10 –
Indoor capacity code
(Equivalent to capacity)
7
5 .
9
5 .
1
2
1
5
4 .
1
8
2
1
2
4
2
7
3
0
3
6
4
2
4
8
5
4
7
2
9
6
120
EN
EN
ID
20-EN