The piping is supported.
All piping connections must prevent the propagation of
noise and be flexible.
4.3.2 Discharge
NOTICE
Improper fitting of the discharge pipe.
Leaks and flooding of the installation room!
B The pumping station must not be used as
a control point for piping.
B Do not connect other drain pipes to the
discharge pipe.
Use pressure pipes (minimum PN6) for the discharge
pipe. The pressure reaches 2 bar at the station outlet.
Sanicubic 1 GR HP S: the discharge outlet incorporates a
non-return valve and is fitted with a Ø 50 mm sleeve.
Sanicubic 2 GR HP S: the discharge outlet of each mo-
tor incorporates a non-return valve. They are joined by a
Ø 50 mm Y-sleeve.
To prevent the risk of back-flow of water from the sewer,
install the discharge pipe in a «loop» so that its base, at
the highest point, is located above the back-flow level.
IMPORTANT
Fit a shutoff valve behind the check valve.
4.3.3 Ventilation
According to the recommendations of EN 12050-1, it must
be equipped with a vent above the roof. The pumping
station must always be ventilated so that the tank is
always at atmospheric pressure. The ventilation must be
completely free and air must flow in both directions (no
diaphragm valve fitted).
NOTICE
Insufficient ventilation.
Risk that the pumping station will not work!
B Do not connect to a
controlled ventilator.
B Ventilation must remain free.
B Do not block the vent outlet.
B Do
not
install
(diaphragm valve).
• Connect the ND50 vent pipe vertically to the vent
opening with the flexible couplings. The connection
must be smell-proof.
• The vent pipe must not be connected to the vent pipe
on the inlet side of a grease trap.
4.4 ELECTRICAL CONNECTION
DANGER
B Do not make the electrical connection
until the final connections are completed.
DANGER
Electrical connection work performed by
an unqualified individual.
Risk of death by electric shock!
B The electrical connection must be performed
by a qualified and licensed electrician.
B The electrical installation must meet the
current standards in the country.
NOTICE
Wrong supply voltage.
Damage to the pumping station!
B The supply voltage must not differ by
more than 6% of the rated voltage specified
on the rating plate.
mechanically
an
air
intake
valve
Sanicubic GR HP S is powered by the control box: see
4.5.1 Control box intallation.
4.5 INSTALLATION OF CONTROL AND ALARM
BOXES
4.5.1 Control box intallation
• The control box must be installed indoors, in a place
protected from humidity and frost.
• Install the control box at least 1 m from the ground.
• Connect the control box to the power supply:
The device's power supply must be connected to ground
(class I) and protected by a high sensitivity differential
circuit breaker (30 mA).
The connection must be used exclusively to provide the
power to the control box. If the cord of this device is
damaged, it must be replaced by the manufacturer or its
after-sales service in order to avoid any danger to users.
• Connect under the control box:
- the pump(s) connector(s),
- the pressure switch connector,
- the hose for Control box ventilation.
4.5.2 Alarm box installation
• The alarm box must be installed indoors, in a damp-
free location.
• The alarm signal must always be visible to the user.
• Connect the jack to the bottom of the external alarm
box.
Note: If the jack plug is incorrectly inserted, the external
alarm box will signal a power failure (see 8.2 Operation).
5. COMMISSIONING
Once the plumbing and electrical connections have been
made, check that the connections are watertight by
letting water flow successively through each inlet used.
Make sure that the unit is operating correctly by carrying
out at least two start cycles with water to test the system.
6. USE
NOTICE
B In the event of power failure, stop all
water flow to the appliances connected to
the Sanicubic GR HP S.
WARNING
Hot surface.
Burn Hazards!
 Never touch the surface of the motor
housing without protective equipment.
Limit of use
DANGER
Pressure and temperature limits exceeded.
Leakage of hot or toxic fluid!
B Observe the operating specifications in
the documentation.
B Avoid running the pump with the valve
closed.
B Dry running, without pumped fluid, must
be avoided.
When in use, observe the following parameters and
values:
PARAMETER
Flow rate
Do not exceed (for all appliances)
80% of the flow rate indicated on the
curve (see attached instructions).
14
VALUE
loading