INSTALLATION
Turning direction check
1 Check the turning direction of the operator using
the mini-pushbuttons PUL1 (close) and PUL2 (open).
Connection of safety transmitter-receiver photocells in closing (SG.C) with testing
Connection of safety transmitter-receiver photocells in opening (SG.A) with testing
5

LIMIT SWITCHES CONNECTION

O
The gate is halted at the end of the operation by way
of the FCA and FCC limit switches. It is therefore
24
Installation Guide
2 If the turning direction is not correct, interchange
FT06
1 Complete the connections as shown in the figure.
2 Place DIP9 in ON (closing photocell testing enabled).
O
O
O
P121I
FT06
1 Complete the connections as shown in the figure.
2 Place DIP6 in ON (opening photocell testing
O
O
O
P121J
the cables connected in cable connectors RL1 and
RL2.
We recommend installing opening and closing
safety photocells.
If the photocells are not connected to carry out
testing, place DIP9 in OFF.
If a magnetic strip is installed instead of a photocell,
place DIP9 in OFF.
If neither photocells nor a mechanical strip are
connected, make an electrical bridge between the
COM and SG.C cable connectors and place DIP9 in
OFF.
We recommend installing opening and closing
safety photocells.
enabled).
If the photocells are not connected to carry out
testing, place DIP6 in OFF.
If a magnetic strip is installed instead of a photocell,
place DIP6 in OFF.
If neither photocells nor a mechanical strip are
connected, make an electrical bridge between the
COM and SG.A cable connectors and place DIP6 in
OFF.
necessary to always install FCC and FCA and
adjust them accordingly.