Hole Pattern for Custom Mounting
1.67"
2"
1.67"
NOTICE: In order to maintain IP66/IP67 protection in
custom installations, watertight seals must be used
under the heads of the four mounting bolts and they
must be retained by a lock washer and nut on the inside
of the box or panel. Alternatively, four blind holes can
be drilled and threaded to accommodate #8-32 x 5/8"
mounting screws. The hole depth must be sufficient to
achieve adequate gasket compression.
Achieving rated watertightness
Rated IP66 /IP67 watertightness to is achieved when
the plug and receptacle are mated. When disconnected,
the receptacle cap must be fully inserted with the slot
in the cap aligned with the protruding 'button'.
The plug cap must be pressed firmly into place.
NOTICE: Proper steps must be taken to maintain
watertightness at threaded connections on the plug
handles or at the junction box. The use of a sealer tape
is recommended.
Attaching the handle
Insert cable through cable gland and handle before
tightening the phase conductor. Assemble handle with
the screws and gasket supplied, (use short screws for
inlets, long screws for receptacles) and tighten cable
gland with an appropriate tool.
NOTICE: MELTRIC threaded lugs are required for use
with handles.
Attaching the metal angle (if required)
Attach receptacle or inlet to metal angle using the
screws and gasket supplied, (use short screws for
inlets, long screws for receptacles).
metal angle to ground. Apply a torque of 17 in-lbs
(2 N.m.) to each screw.
Assembly of the plug/inlet cap
Attach the cap to the plug /inlet by retaining the end of
the chain under one of the mounting screws.
Gasket
In order to achieve rated watertightness, the flat black
gasket must be installed between the inlet or receptacle
and the panel or accessory to which itis attached.
When assembling the inlet or receptacle to the side of
an enclosure, the isolating ring must be positioned as
indicated on Figure 1.
A
1
A: Color-coded ring
B: Isolating ring
C: Flat color-coded gasket
Rated current and voltage markings
Ø.201 thru or
It is essential to indicate the current and voltage of the
tap for 10-32
main circuit on the supplied stickers. Apply the stickers
on or adjacent to the product so they can easily be seen.
OPERATION
To ensure safe and reliable operation, MELTRIC
plugs and receptacles must be used in accordance
with their assigned ratings.
SP devices can only be used in conjunction with mating
WARNING
receptacles or plugs manufactured by MELTRIC
another licensed producer of products bearing the
DANGER
NOTICE: Do not attempt to operate the SP device until
CAUTION
the receptacle is mounted. The mounting bolts must
be in place to maintain alignment of components and
NOTICE
compression against the panel or handle is required to
maintain assembly.
ADVERTENCIA
SP series plugs and receptacles feature different
DANGER
mechanical keying of L1, L2, L3, N, and G. Mating
plug /receptacle combinations are color coded for easy
identification.
CAUTION
SP series plugs and receptacles are not intended to
AVISO
be connected or disconnected under load. The pilot
circuit must be used to control the power circuit.
The pilot circuit can only be turned 'on' when the
WARNING
plug is engaged and the plug can only be removed
when the pilot curcuit is in the 'off' position.
DANGER
safety, MELTRIC recommends the following connection
sequence: Ground, Neutral, Phase 1, Phase 2, Phase 3.
CAUTION
Connection
NOTICE
Insert the plug straight into the receptacle until a 'click'
is heard. Figure 2 The plug and its flexible cable must
not exert force on the receptacle.
ADVERTENCIA
DANGER
CAUTION
AVISO
Connect the
WARNING
DANGER
CAUTION
NOTICE
Pull on the plug to make sure it is properly latched in
ADVERTENCIA
the receptacle. Figure 3. A small rotation of the plug,
in either direction, engages the locking finger on the
DANGER
receptacle to prevent any further rotation.
CAUTION
AVISO
To close the pilot circuit
and mechanically lock the
plug into the receptacle,
turn the ring on the recep-
tacle until the "1" lines
up with the arrow across
from the release button.
Figure 4.
Do not attempt to
turn the ring towards
"1" when there is no plug engaged. Defeating the
C
mechanical lock could create a potentially hazardous
B
WARNING
condition if energized under load.
DANGER
CAUTION
NOTICE
ADVERTENCIA
DANGER
CAUTION
technology trademark.
2
3
4
Disconnection
To open the pilot circuit and unlock the plug, turn the
ring back until the "0" is aligned with the arrow.
Figure 5. This action signals the controller to switch off
the power and unlocks the plug. To remove the plug,
press firmly on the latch release button and
simultaneously pull on the plug. A slight rotation of
the plug may be required before it can be removed.
®
5
or
®
MAINTENANCE
WARNING: Before inspecting, repairing, or maintaining
MELTRIC products, disconnect electrical power to the
receptacle to eliminate the risk of electrical shock.
MELTRIC products require little on-going maintenance.
However, it is a good practice to periodically perform
the following general inspections:
• Check the mounting screws for tightness.
• Verify that the weight of the cable is supported
by the strain relief mechanism and not by the
terminal connections.
For
• Check the IP gaskets for wear and resiliency.
Replace as required.
WARNING
• Verify the electrical continuity of the ground circuit.
DANGER
• Check the contact surfaces for cleanliness
CAUTION
and pitting.
NOTICE
Use a clean cloth to rub off deposits of dust or similar
ADVERTENCIA
foreign materials on the contacts and the plug interiors.
DANGER
Sprays should not be used, as they tend to collect dirt.
CAUTION
If any significant pitting of the contacts or other serious
damage is observed, the device should be replaced.
AVISO
MANUFACTURER'S RESPONSIBILITY
MELTRIC's responsibility is strictly limited to the repair
or replacement of any product that does not conform
to the warranty specified in the purchase contract.
MELTRIC shall not be liable for any penalties or
consequential damages associated with the loss of
production, work, profit, or any other kind of financial
loss incurred by the customer.
MELTRIC Corporation shall not be held liable when
its products are used in conjunction with products not
bearing the
of MELTRIC products in conjunction with mating devices
that are not marked with the
trademark shall void all warranties on the product. For
the latest revision of our documents, visit meltric.com.
MELTRIC Corporation is an ISO 9001 certified company.
Its products are designed, manufactured and rated in
accordance with applicable UL, CSA and IEC standards.
MELTRIC designs and manufactures its products in
accordance with Marechal keying standards established
to ensure intermatablility with similarly rated products
manufactured by Marechal Electric Group.
Latch
Release
Button