4.6.4.2
DIP-switch setting possibilities
NOTE
The cooling unit carries voltage if the red LED light on the controller is flashing. Always make sure that there is no voltage on
the unit before carrying out any work on the electrical connections.
DIP-switch
1
2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Tab. 9: DIP-switch setting possibilities
NOTE
The cooling unit must be switched off and on to accept the changed setting.
Operating Manual | Attachment and Installation Cooling Units | Standard Controller (SC) – 230 V | 086100119
Temperatures in °C
DIP-switch 4 OFF
3
Setpoint
OFF
25 °C
OFF
30 °C
OFF
35 °C
OFF
35 °C
ON
40 °C
ON
40 °C
ON
45 °C
ON
45 °C
Max. limit
Setpoint
45 °C
77 °F
45 °C
86 °F
45 °C
95 °F
50 °C
95 °F
50 °C
104 °F
55 °C
104 °F
55 °C
113 °F
60 °C
113 °F
Temperatures in °F
DIP-switch 4 ON
Max. limit
113 °F
113 °F
113 °F
122 °F
122 °F
131 °F
131 °F
140 °F
39/66