2.4.
Battery replacement
Notice: This UPS is equipped with internal batteries and user can replace the batteries without shutting down the UPS or
connected loads.(hot-swappable battery design) Replacement is a safe procedure, isolated from electrical hazards.
CAUTION!! Consider all warnings, cautions, and notes before replacing batteries.
Note: Upon battery disconnection, equipment is not protected from power outages.
Step 1
Remove front panel.
Step 4
Remove the top cover of
battery box and replace
the inside batteries.
Step 7
Put the front panel back to the unit.
Segurança e harmonia
ININTERRUPTA
Step 2
Disconnect battery wires.
Step 5
After replacing the batteries,
put the battery box back to
original location and screw it tightly.
.
PH 9310 | PH 9315 | PH 9320 | PH 9330
2. Installation and setup
Step 3
Pull out the battery box by
removing two screws on
the front panel.
Step 6
Re-connect the battery wires.
Uninterruptible Power Supply
EN
41