Display Options; Rotating The Display - Tripp-Lite PDU3XMV6G32 Manual Del Propietário

Unidad de distribución de energía trifásica con medidor digital de 0u
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Using the Digital Display
BANK INDICATOR LED DEFINITIONS:
LED Configuration
Standard
1
Alternate
1
This is the default configuration.

Display Options

LED Test
Hold the Mode button for 3 seconds to test the display. For 5 seconds, all LEDs and display
segments will light green, while all Load Indicator LEDs will light yellow. Please visit
www.tripplite.com/support for issues with display segment or Indicator LED functionality.

Rotating the Display

0 3.0
0 i
14-08-206-93338E.indb 11
LED Color
Bank Status
Off
Off
Green
On
Yellow
On
Red
Off
Red Flashing
Off
Off
Off
Red
On
Red Flashing
On
Green
Off
Green Flashing
Off
8 8 8
88
Description
Bank power is absent
Circuit breaker is on – Bank power is present
Bank has exceeded 80% of its current rating –
Bank power is present
Bank is below the Low Voltage threshold –
Bank is disabled
Circuit breaker has tripped – Bank power is absent
Bank power is absent
Circuit breaker is on – Bank power is present
Bank has exceeded 80% of its current rating –
Bank power is present
Bank is below the Low Voltage threshold –
Bank is disabled
Circuit breaker has tripped – Bank power is absent
At any point, pressing both of the arrow
buttons simultaneously and holding for
3 seconds rotates the 2-digit and 3-digit
displays.
11