Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Using the Digital Display
OUTLET INDICATOR LED DEFINITIONS:
LED Configuration
Standard
1
Alternate
1 This is the default configuration.

Display Options

LED Test
Hold the Mode button for 3 seconds to test the display. All LEDs and display segments will light
green, while all Load Indicator LEDs will light yellow. Please visit www.tripplite.com/support for
issues with display segment or Indicator LED functionality.
Viewing the IP Address
i P
i
13-09-017-9332B8.indb 15
LED Color
Outlet Status
Off
Off
Green
On
Yellow
On
Red
Off
Red Flashing
Off
Off
Off
Red
On
Red Flashing
On
Green
Off
Green Flashing
Off
8 8 8
88
At any point, pressing both of the arrow buttons simultaneously for 1/2
second displays the unit's IP address in the 2-digit display.
To Rotating the Display
Description
Outlet power is absent
Circuit breaker is on – Outlet power is present
Outlet current has exceeded 80% of the outlet
current rating – Outlet power is present
Outlet voltage is below the Low Voltage threshold –
Outlet power is absent
Circuit breaker has tripped – Outlet power is absent
Outlet power is absent
Circuit breaker is on – Outlet power is present
Outlet current has exceeded 80% of the outlet
current rating – Outlet power is present
Outlet is disabled - Outlet power is absent
Circuit breaker has tripped – Outlet power is absent
15
9/5/2013 4:26:57 PM
Tabla de contenido
loading

Tabla de contenido